Setpt, 00 sptstout, Value sptson – Red Lion CUB5T User Manual

Page 10: Value sptsoff, Off sptsp-up, No stop-t, No autosrst, Yes sptsrst, No ch-color, 4 module 4 - s

Advertising
background image

10

SAVE

will restore the output to the same state it was at before the meter was

powered down.

ON

will activate the output at power up.

OFF

will deactivate the

output at power up. This parameter is not active when the Setpoint Action is
selected for timed output mode.

SETPOINT OUTPUT POWER-UP STATE

Stops the Timer when the Setpoint output activates (

OUt-ON

) or deactivates

(

OUt-OFF

). Select

NO

if the output should not affect the Timer Run/Stop status.

The Timer Stop condition is cleared when a Timer Reset occurs, or a Time

Start edge is applied on the Timer input.

STOP TIMER

SETPOINT OUTPUT TIME-OUT

SPT ACTION DESCRIPTION

OUTPUT ACTIVATES

OUTPUT DEACTIVATES

LAtCH

Latched Output Mode

When Time or Count

= Setpoint On value

At Manual Reset

(if

SPt rSt

=

YES

)

t-OUt

Timed Output Mode

When Time or Count

= Setpoint On value

After Setpoint

Output Time-Out

ON-OFF

On-Off Output Mode

When Time or Count



Setpoint On value

When Time or Count



Setpoint Off value

This parameter is only active if the Setpoint Action is set to Timed Output

mode (



). Enter the time duration the Setpoint Output will remain ON once

it is activated. This value is always entered in minutes, seconds, and hundredths
of seconds format. The maximum value is 99 minutes 59.99 seconds.

00.00.01

to

99.59.99

SETPOINT ON

This parameter determines when the Setpoint output will activate. The output

can activate at a programmed Setpoint Value or can be set to activate when the
Timer starts (

t-Strt

) or stops (

t-StOP

).

Selecting

VALUE

displays a sub-menu where the Setpoint Value is entered. If

the Setpoint is assigned to the Timer, the value is entered in the same display
format as the selected Timer Range.

Automatically resets the Setpoint Assigned display value when the Setpoint

Output activates (

OUt-ON

) or deactivates (

OUt-OFF

). Select

NO

if the output should

not cause a display reset.

TIMER/COUNTER AUTO RESET

Select

YES

to have the Setpoint Output deactivate (reset) when the Setpoint

Assigned display resets. Reset can occur by the RST button or the User Input,
if programmed for that function. Select



if the Setpoint output should not

reset when the display resets.

SETPOINT OUTPUT RESET WITH DISPLAY RESET

This parameter enables the backlight CUB5T to switch the display color when

the Setpoint output activates. When the output deactivates, the display color will
revert to the normal operating mode color. This parameter is only active for the
backlight version.

CHANGE DISPLAY COLOR w/SETPOINT OUTPUT STATE

00.01.00

SPtstOUt

VALUE

SPtsON

SETPOINT OFF

The Setpoint Off parameter only appears if the Setpoint Action is set to

On-Off Output mode (

ON-OFF

). In this mode, the Setpoint OFF parameter

determines when the Setpoint Output will deactivate. The output can be
programmed to deactivate at a Setpoint Off Value or can be set to deactivate
when the Timer starts (

t-Strt

) or stops (

t-StOP

).

Selecting

VALUE

displays a sub-menu where the Setpoint Off Value is entered.

If the Setpoint is assigned to the Timer, the value is entered in the same display
format as the selected Timer Range.

VALUE

SPtsOFF

OFF

SPtsP-UP

NO

StOP-t

NO

AUtOsrSt

YES

SPtsrSt

NO

Ch-COLOr

NO

Out-ON

Out-OFF

NO

YES

YES

NO

Out-OFF

Out-ON

NO

SAVE

ON

OFF

6.4 MODULE 4 - S

ETPOINT

O

UTPUT

P

ARAMETERS

(

4-SEtPt

)

SEL

Backlight

Unit Only

Pro

Setpoint

Output Action

Setpoint

Assignment

Setpoint On

Timer/Counter

Auto Reset

Setpoint Off

Stop Timer

Setpoint

Output

Time-out

Setpoint

Output Reset

with Display Reset

Change Display

Color with

Setpoint Output

State

SPt ASN

4-SEtPt

SPt ACt

SPt ON

SPt OFF

SPt tOUt

StOP-t

AUtO rSt

SPt rSt

Ch-COLOr

Setpoint Output

Power-up

State

SPt P-UP

PARAMETER MENU

The Setpoint Output Parameters are only active when the optional relay

module is installed in the meter. Some parameters will not appear depending on
the Setpoint Assignment and Setpoint Output Action selected.

Select the display for Setpoint assignment.

SETPOINT ASSIGNMENT

C-VALUE

t-VALUE

t-VALUE

SPtsASN

SETPOINT OUTPUT ACTION

This parameter selects the action of the Setpoint output as shown below.

LAtCH
t-OUt
ON-OFF

LAtCH

SPtsACt

t-StOP

t-Strt

VALUE

t-StOP

t-Strt

VALUE

0000000

to

9999999

0000100

SPt

VAL

0000000

to

9999999

0000200

SPOF

VAL