6.2 MODULE 2 - C

YCLE

C

OUNTER

P

ARAMETERS

(

2-Count

)

SEL

Cycle Counter

Count Source

Cycle Counter

Enable

Cycle Counter

Counting
Direction

Cycle Counter

Start Value

Cycle Counter

Reset At

Power-up

2-Count

Cnt Enb

Cnt Src

Cnt dir

Cnt Strt

RSt P-UP

Pro

PARAMETER MENU

CYCLE COUNTER ENABLE

When set to

NO

, the remaining Cycle Counter parameters are not accessible.

This parameter selects the source from which the Cycle Counter derives

counts. The Timer Reset

(

t-rESEt

)

selection generates a count when either a

manual or automatic timer reset occurs (See Module 4 for programming
Automatic Reset). The Input B (

INPUt b

) selection generates a count each time

Input B is activated. This selection overrides the timer inhibit function of Input
B, when the timer is programmed for Level or Edge-1 operating mode (See
Module 1 for Timer Input Operating Modes).

The User Input

(

USr1NP

)

selection generates a count each time the User Input

is activated. When selected as the count source, the User Input can still be set
to perform a User Function described in Module 1. In this case, the Cycle
Counter will count the number of times the selected User Function occurred.

The Output ON/OFF selections generate a count when the Setpoint output

either activates or deactivates. These selections will only generate counts when
an optional Setpoint module is installed.

CYCLE COUNTER COUNT SOURCE

t-rESEt

OUt-ON
OUt-OFF

INPUtsb
USrsINP

CYCLE COUNTER START VALUE

CYCLE COUNTER COUNTING DIRECTION

Bi-directional counting capability. Select the counting direction desired for

the application.

The Cycle Counter returns to this value whenever a Counter Reset occurs.

Non-zero values are normally used for “down counting” applications, but can
also provide an offset value when counting up.

UP dn

000000

to

999999

USER INPUT ASSIGNMENT

The User Input Assignment only applies if the cycle counter is enabled and

a selection of reset, display hold, hold and reset, inhibit, or print and reset is
selected in the User Input Function menu.

USER INPUT FUNCTION

USER INPUT FUNCTION (Cont’d)

MODE

DISPLAY

No Function

NO

DESCRIPTION

User Input disabled.

Program Mode Lock-out

Pro Loc

Display Select
(Edge triggered)

d-SELECt

Toggle display with each
activation.

Maintained Reset

rESEt

Level active reset of the
selected value(s).

Display Hold

d-HOLd

Hold and Reset

HOLd-rSt

Edge triggered reset of the
selected value(s) after
storing the time or count.

t-VALUE

C-VALUE

both t-C

See Programming Mode
Access chart (Module 3).

Freeze display for the selected
value(s) while allowing time or
counts to accumulate internally.

NO

USErsINP

t-VALVE

USErsASN

YES

CntsEnb

UP

Cntsdir

t-rESEt

CntsSrc

000000

CntsStrt

CYCLE COUNTER RESET AT POWER-UP

The Cycle Counter can be programmed to Reset at each meter power-up.

NO

YES

NO

RStsP-UP

YES

NO

NO

YES

TIMER RESET AT POWER-UP

The Timer can be programmed to Reset at each meter power-up.

YES

RSt

s

P-UP

Print

Serial transmit of the active
parameters selected in the Print
Options menu (Module 5).

Print Request

r5t OUt

Prnt-r5t

Edge triggered deactivation of
the Setpoint Output.

Same as Print Request followed
by a momentary reset of the
selected value(s).

Reset Output

Print and Reset

Inhibit

Inhibit timing or counting for the
selected value(s).

d-LEVEL

Increase intensity one level
for each activation. (backlight
version only)

DISPLAY

DESCRIPTION

Inhibit

Display Intensity Level
(Edge Triggered)

MODE

Advertising