Input, 1 module 1 - t, Level input – Red Lion CUB5T User Manual

Page 7: On filter, Up t-dir, Yes t-flash, No t-stop, Stop run, P-up, Imer

Advertising
background image

Timer Input

Operation

Timer Input

Filter

Timer Run

State At

Power-up

Timing

Direction

Timer Start

Value

Flash Timer

Annunciator

Timer Reset

At Power-up

Timer
Range

SEL

RANGE

INPUt

OP

FILtEr

t-dir

t-Strt

t-FLASH

Run P-UP

RSt P-UP

1-INPUt

Pro

USEr INP

User Input

Function

USEr ASN

User Input

Assignment

t-StOP

Timer Stop

Value

7

6.1 MODULE 1 - T

IMER

I

NPUT

P

ARAMETERS

(

1-INPUt

)

PARAMETER MENU

5555555

RANGE

This parameter determines how the Timer Input Signals affect the Run/Stop

status of the Timer. Timing diagrams are shown below for level active and edge
triggered (1-input or 2-input) operation. For single input modes (Input A only),
Input B provides a level active Timer Inhibit function. In the Display Hold
mode, the timer display value remains held and only updates when a Timer
Start (Input A) or Timer Stop (Input B) edge occurs.

The timer reset (

rSt

) operating modes are identical to the other modes in the

diagrams, except the timer display value is reset at the Time Start edges.

The Timer can also be stopped at a Timer Stop Value or at Setpoint output

activation or deactivation. This type of Stop condition is cleared when a Timer
Reset occurs, or another start edge is applied on the timer input.

For Reset Modes (

rSt

), the timer is reset at Time Start edge.

18 TIMER RANGE SELECTIONS

(S

= SEC;

N

= MIN;

H

= HR;

d

= DAY

))

TIMER RANGE

LEVEL

INPUt

s

OP

Level Active (Gated) Operation

INPUT A

INPUT B - Timer Inhibit (Level Active)

Time
Start

Time

Stop

Time
Start

Time

Stop

Edge Triggered Operation -1 Input

INPUT A

INPUT B - Timer Inhibit (Level Active)

Time
Start

Time

Stop

Time
Start

Time

Stop

Ed9E-1

,

Ed-1srSt

LEVEL

,

LEVsrSt

TIMER INPUT OPERATION

HHHHH.HH

99999.99

0.01 HR

HHHHHHH

9999999

1 HR

HHHHHH.H

999999.9

0.1 HR

HOURS

NNNNNN.N

999999.9

0.1 MIN

NNNNN.NN

99999.99

0.01 MIN

MINUTES

NNNNNNN

9999999

1 MIN

55555.55

99999.99

0.01 SEC

5555.555

9999.999

0.001 SEC

5555555

9999999

1 SEC

555555.5

999999.9

0.1 SEC

MAXIMUM

DISPLAY

DISPLAY

RESOLUTION

RANGE

SELECTION

SECONDS

DAYS/HOURS/MINUTES

ddd.HH.NN

999.23.59

1 MIN

HHH.NN.SS

999.59.59

1 SEC

HOURS/MINUTES/SECONDS

HHHH.NN.N

9999.59.9

0.1 MIN

HHH.NN.NN

999.59.99

0.01 MIN

HOURS/MINUTES

HHHHH.NN

99999.59

1 MIN

NNN.SS.SS

999.59.99

0.01 SEC

NNNNN.SS

99999.59

1 SEC

NNNN.SS.S

9999.59.9

0.1 SEC

MAXIMUM

DISPLAY

DISPLAY

RESOLUTION

RANGE

SELECTION

MINUTES/SECONDS

LEV

s

rSt

LEVEL

Ed-1

s

rSt

Ed9E-1

HOLd

s

rSt

HOLd-2

Ed-2

s

rSt

Ed9E-2

ON

OFF

TIMING DIRECTION

Bi-directional timing capability. Select the timing direction desired for the

application.

0000000

to

9999999

ON

FILtEr

UP

t-dir

0000000

t-Strt

TIMER INPUT FILTER

Provides a 50 msec software debounce for the Timer Inputs (A and B). Select

ON

when using relays or switch contacts as a signal source.

TIMER START VALUE

The Timer returns to this value whenever a Timer Reset occurs. The value is

entered in the same display format as the Timer Range selected. Non-zero
values are normally used for “timing down” applications, but they can also
provide an offset value when timing up.

Edge Triggered Operation - 2 Input

INPUT A

INPUT B

Time
Start

Time
Start

Time

Stop

Time

Stop

Edge Triggered Operation - 2 Input,
with Display Hold

INPUT A

INPUT B

Time Stop,

Display Update

Time Start,

Display Update

Time Start,

Display Update

Display
Update

HOLd-2

,

HOLdsrSt

Ed9E-2

,

Ed-2srSt

dn

UP

NO

YES

FLASH TIMER ANNUNCIATOR

Select

YES

to have the timer annunciator (

t

) flash when the timer is running.

YES

t-FLASH

NO

YES

TIMER STOP VALUE

The Timer stops when this value is reached regardless of the signal levels on

the timer inputs. Selecting

YES

displays a sub-menu where the Stop Value is

entered in the same display format as the Timer Range selected. This stop
condition is cleared when a Timer Reset occurs or another start edge is applied
on the timer input. Select

NO

if a Stop Value is not desired.

NO

t-StOP

StOP

SAVE

TIMER RUN STATE AT POWER-UP

Determines the Run/Stop state of the Timer at Power-up. This parameter

does not apply to

LEVEL

Input Operation.

StOP

- Timer Stopped at power-up, regardless of prior Run/Stop state

SAVE

- Timer assumes the Run/Stop state it was in prior to power-down

StOP

Run

s

P-UP

0000000

to

9999999

0000000

StOP

VAL