DATA BIT

ABBREVIATED PRINTING

PRINT OPTIONS

PARITY BIT

METER ADDRESS

300

1200

600

2400

19200
38400

4800
9600

7-bit

8-bit

NO

Odd

EVEN

NO

YES

NO

YES

Module 5 is the programming module for the Serial Communications

Parameters. These parameters are used to match the serial settings of the
CUB5T with those of the host computer or other serial device. The Serial Setup
Parameters are only accessible when an optional RS232 or RS485 serial
communications module is installed in the meter.

This section replaces the bulletin shipped with the RS232 and RS485 serial

communications plug-in cards. Discard the separate bulletin when using those
serial plug-in cards with the CUB5T.

SEL

Data Bit

Baud Rate

Parity Bit

Print

Options

Meter

Address

Abbreviated

Printing

5-SEriAL

bAUd

dAtA

PAritY

Addr

Abbr

Prnt OPt

Copy Program

Settings

COPY

Pro

6.5 MODULE 5 - S

ERIAL

C

OMMUNICATIONS

P

ARAMETERS

(5-SEriAL)

PARAMETER MENU

BAUD RATE

Set the baud rate to match that of other serial communications equipment.

Normally, the baud rate is set to the highest value that all of the serial
communications equipment is capable of transmitting and receiving.

Select either 7- or 8-bit data word length. Set the word length to match the

other serial communications equipment on the serial link.

This parameter only appears when the Data Bit parameter is set to a 7-bit

data word length. Set the parity bit to match that of the other serial equipment
on the serial link. The meter ignores parity when receiving data and sets the
parity bit for outgoing data. If parity is set to

NO

, an additional stop bit is used

to force the frame size to 10 bits.

Enter the serial node address. With a single unit, an address is not needed

and a value of zero can be used (RS232 applications). Otherwise, with multiple
bussed units, a unique address number must be assigned to each meter. The
node address applies specifically to RS485 applications.

This parameter determines the formatting of data transmitted from the meter

in response to a Transmit Value command or a Block Print Request. Select

NO

for a full print transmission, consisting of the meter address, mnemonics, and
parameter data. Select

YES

for abbreviated print transmissions, consisting of the

parameter data only. This setting is applied to all the parameters selected in the
PRINT OPTIONS. (Note: If the meter address is 0, the address will not be sent
during a full transmission.)

9600

bAUd

7-bit

dAtA

Odd

PAritY

00

Addr

NO

Abbr

NO

Prnt OPt

0

to

99

This parameter selects the meter values transmitted in response to a Print

Request. A print request is also referred to as a block print because more than
one parameter can be sent to a printer or computer as a block.

Selecting

YES

displays a sublist for choosing the meter parameters to appear

in the print block. All active parameters entered as

YES

in the sublist will be

transmitted during a block print. Parameters entered as

NO

will not be sent.

The “Print All” (

Prnt ALL

) option selects all meter values for transmitting

(

YES

), without having to individually select each parameter in the sublist.

Note: Inactive parameters will not be sent regardless of the print option

setting. For example, the Cycle Counter and Cycle Counter Start values will
only be sent when the Cycle Counter is enabled. If disabled, these parameters
are inactive and will not be transmitted. Likewise, the Setpoint parameters will
not be sent unless an optional setpoint card is installed in the meter.

DISPLAY

MNEMONIC

t-VALUE

Timer

YES

TMR

C-VALUE

Cycle Counter

NO

CNT

t-StOP

t-Strt

Timer Stop

Timer Start

NO

NO

TSP

TST

Cnt Strt

NO

CST

SPt ON

NO

SPT

SPt tOUt

SPt OFF

Setpoint Time-out

Setpoint OFF

NO

NO

STO

SOF

DESCRIPTION

FACTORY

SETTING

Counter Start

Setpoint ON