Universal and Analog Inputs

Name Description

Range

Name

Get 0 to 100% regardless of direction

0% to 100%

NameLo

Get 0 to 100% of Min to (Center -
Deadband) only if Center is enabled

0% to 100%

NameHi

1

Get 0 to 100% of (Center + Deadband)
to Max only if Center is enabled

0% to 100%

Name.Dir

Get the Upper or Lower Side of the
Analog Input only if Center is enabled.

False (Lower Side), True (Upper Side)

Name.RawVolts

Volts or mAmps (ma = universal input
ma select)

0 to 1023 * Scale

Name.RefVolts

Reference Volts = RefVolts * .00489

0 to 1023

Name.RampVolts

Ramped Volts = RampVolts * Scale
Factor

0 to 1023 * Scale

Name.MinVolts

When Name = 0% (i.e. Center not
enabled)

0 to 1023 * Scale

Name.MaxVolts

When Name = 100%

0 to 1023 * Scale

Name.MinLimit

Threshold for Name.MinF

0 to 1023 * Scale

Name.MaxLimit

Threshold for Name.MaxF

0 to 1023 * Scale

Name.RefMinLimit

Threshold for Name.MinRF

0 to 1023 * Scale

Name.RefMaxLimit

Threshold for Name.MaxRF

0 to 1023 * Scale

Name.CenterVolts

Where Center Volts

0 to 1023 * Scale

Name.Deadbandv

Plus and minus volts about CenterVolts

0 to 1023 * Scale

NameX

Where NameX = NameLo, NameHi if
Center is enabled NameX = Name if
Center is not enabled

Name.MinF

Status Flag set if Voltage is less than
Min Limit

False (ok), True (Outside Limit)

Name.MaxF

Status Flag set if Voltage is greater than
Max Limit

Range: False (ok), True (Outside Limit)

Name.MinRF

Status Flag set if Voltage is less than
Reference Min Limit

False (ok), True (Outside Limit)

Name.MaxRF

Status Flag set if Voltage is greater than
Reference Max Limit

False (ok), True (Outside Limit)

Name.LOS

Loss of Signal flag set after time out.
For Universal Pulse inputs Only

False (Pulses ok), True (No Pulse
Input)

Name.RealRPM

The Unsigned Integer Value of the RPM.
For Universal Pulse inputs Only

0 to 9999

Name.Counter

Get/Set Unsigned Integer Value of the
Counter. Universal Pulse inputs Only

0 to 65535

Name.PulsesPerRev

Get/Set Pulses Per Revolution

0 to 9999

Scale depends on Input Range (0 to 5 =.00489, 0 to 10 = .00977, 0 to 25ma = 0.02158 )