onbattery This event is generated 5 or 6 seconds after an initial pow-

erfailure is detected. It means that apcupsd definitely considers the
UPS to be on batteries. The onset of this event can be delayed by the
ONBATTERYDELAY apcupsd.conf configuration directive.

Default — does a printf ‘‘Power failure.

Running on UPS

batteries.’’

| wall

then exits.

offbattery This event is generated when the mains return only if the

onbattery event has been generated.

Default — does nothing.

powerout This event is generated immediately when apcupsd detects that

the UPS has switched to batteries. It may be due to a short power-
failure, an automatic selftest of the UPS, or a longer powerfailure. In
many cases, you may want to inhibit the normal message sent/emailed
by this event to avoid being annoyed by short power failures.

Default — does a printf ‘‘Warning power loss detected.’’

|

wall

then exits.

remotedown This event is generated on a slave machine when it detects

either that the master has shutdown, or that a onbattery situation
exists and the communications line has been severed. Despite the
name, you should never reboot the machine — instead always shut it
down.

Does a shutdown -h now

restartme This event is depreciated and should not be used.

Terminates the currently running apcupsd and then restarts it.

runlimit This event is generated when the MINUTES value defined in

the apcupsd.conf file expires while in a power fail condition. The
MINUTES is the remaining runtime as internally calculated by the
UPS and monitored by apcuspd.

Does a printf ‘‘UPS battery runtime percent reached.

Doing

shutdown.

\n’’ | wall then exits.

After completing this event,

apcupsd will immediately initiate a doshutdown event.

timeout This event is generated when the TIMOUT value defined in the

apcupsd.conf file expires while in a power fail condition. It indicates
that the total time in a power failure has been exeeded and the machine
should be shutdown. Normally, with smart UPSes, this value is not
used, but rather one relies on the remaining runtime (MINUTES) or
the battery level (BATTERYLEVEL) values specified in the conf file.