Back-ups office 500 signals, Analyses of apc cables, The back-ups office 500 signals – APC UPS control system User Manual

Page 144

Advertising
background image

Note 2: the same as note 1 except that the line is normally closed,

and opens when the line voltage fails.

The Back-UPS Office 500 signals

The Back-UPS Office UPS has a telephone type jack as output, which looks
like the following:

Looking at the end of the connector:

6 5 4 3 2 1

_____________

| . . . . . . |
|

|

|

|----------|

|__|

It appears that the signals work as follows:

UPS

Signal meaning

1 (brown)

<-

Shutdown when set by computer for 1-5 seconds.

2 (black)

->

On battery power

3 (blue)

->

Low battery

4 (red)

Signal ground

5 (yellow)

<-

Begin signalling on other pins

6 (none)

none

Analyses of APC Cables

940-0020B Cable Wiring:

This diagram is for informational purposes and is not complete. Although
we do not know what the black box semi-conductor contains, we believe that
we understand its operation (many thanks to Lazar M. Fleysher for working
this out).

This cable can only be used on voltage-signalling UPSes, and provides the
On Battery signal as well as kill UPS power. Most recent evidence (Lazar’s