Voltage signalling, Supported features – APC UPS control system User Manual

Page 143

Advertising
background image

Voltage Signalling Features Supported by Apcupsd for Vari-
ous Cables

The following table shows the features supported by the current version
of apcupsd (3.8.5 or later) for various cables running the UPS in voltage-
signalling mode.

Cable

Power Loss

Low Battery

Kill Power

Cable Discon-

nected

940-0020B

Yes

No

Yes

No

940-0020C

Yes

Yes

Yes

No

940-0023A

Yes

No

No

No

940-0119A

Yes

Yes

Yes

No

940-0127A

Yes

Yes

Yes

No

940-0128A

Yes

Yes

Yes

No

940-0095A/B/C

Yes

Yes

Yes

No

simple

Yes

Yes

Yes

No

Voltage Signalling

Apparently, all APC voltage-signalling UPSes have the same signals on the
output pins of the UPS. The difference at the computer end is due to different
cable configurations. Thus, by measuring the connectivity of a cable, one
can determine how to program the UPS. This is to be verified.

The signals presented or accepted by the UPS on its DB9 connector using
the numbering scheme listed above is:

UPS Pin

Signal meaning

1

<-

Shutdown when set by computer for 1-5 seconds.

2

->

On battery power (this signal is normally low but

goes high when the UPS switches to batteries).

3

->

Mains down (line fail) See Note 1 below.

5

->

Low battery. See Note 1 below.

6

->

Inverse of mains down signal. See Note 2 below.

7

<-

Turn on/off power (only on advanced UPSes only)

Note 1: these two lines are normally open, but close when the

appropriate signal is triggered. In fact, they are open collector
outputs which are rated for a maximum of +40VDC and 25 mA. Thus
the 4.7K ohm resistor used in the Custom Simple cable works
quite well.

142

Advertising