Voltage signalling, Supported features – APC UPS control system User Manual
Page 143

Voltage Signalling Features Supported by Apcupsd for Vari-
ous Cables
The following table shows the features supported by the current version
of apcupsd (3.8.5 or later) for various cables running the UPS in voltage-
signalling mode.
Cable
Power Loss
Low Battery
Kill Power
Cable Discon-
nected
940-0020B
Yes
No
Yes
No
940-0020C
Yes
Yes
Yes
No
940-0023A
Yes
No
No
No
940-0119A
Yes
Yes
Yes
No
940-0127A
Yes
Yes
Yes
No
940-0128A
Yes
Yes
Yes
No
940-0095A/B/C
Yes
Yes
Yes
No
simple
Yes
Yes
Yes
No
Voltage Signalling
Apparently, all APC voltage-signalling UPSes have the same signals on the
output pins of the UPS. The difference at the computer end is due to different
cable configurations. Thus, by measuring the connectivity of a cable, one
can determine how to program the UPS. This is to be verified.
The signals presented or accepted by the UPS on its DB9 connector using
the numbering scheme listed above is:
UPS Pin
Signal meaning
1
<-
Shutdown when set by computer for 1-5 seconds.
2
->
On battery power (this signal is normally low but
goes high when the UPS switches to batteries).
3
->
Mains down (line fail) See Note 1 below.
5
->
Low battery. See Note 1 below.
6
->
Inverse of mains down signal. See Note 2 below.
7
<-
Turn on/off power (only on advanced UPSes only)
Note 1: these two lines are normally open, but close when the
appropriate signal is triggered. In fact, they are open collector
outputs which are rated for a maximum of +40VDC and 25 mA. Thus
the 4.7K ohm resistor used in the Custom Simple cable works
quite well.
142