Results of last self test

“OK” - good battery, “BT” -
failed due to insufficient capac-
ity, “NG” - failed due to overload,
“NO” - no results available (no
test performed in last 5 minutes)

Y

Enter smart mode

“SM”

Z—Z

Shutdown immediately (no delay)
- need > 1.5s between first and sec-
ond Z

N/A

a

Show protocol version.alert mes-
sages.valid commands (delimited
by periods)

“3.!$%+?=#—.ˆAˆNˆZ+-

789<@ABCDEFGKLMNOPQRSUVWXYZ’abcefgjklmnopqrsuvzy˜ˆ?”
-

Link-Level.alert-

messages.commands

b

Firmware revision

“50.9.D” - 50 = SKU (vari-
able

length),

9

=

firmware

revision,

D

=

country

code

(D=USA,

I=International,

A=Asia, J=Japan, M=Canada)

c

UPS local id

UPS IDEN (you can program any
8 characters here)

e

Return threshold

% battery charge threshold for re-
turn (00=00%, 01=15%, 02=25%,
03=90%)

f

Battery level %

Ranges - typical “100.0” when
fully charged as should normally
be the case

g

Nominal battery voltage (not ac-
tual voltage - see B)

“012” or “024” or “048”.

h

Measure-UPS: ambient humidity
(%)

“nnn.n” - percentage

i

Measure-UPS: dry contacts

10 = contact 1, 20 = 2, 40 = 3, 80

= 4

j

Estimated runtime at current load
(minutes)

“0112:”

(note, it is terminated

with a colon)

k

Alarm delay

0(zero) = 5 second delay after fail,
T = 30 second delay, L = alarm at
low battery only, N = no alarm

l

Low transfer voltage

Default “103” or “208” in Europe

m

Manufacturing date

Unique within groups of UPSes
(production runs)

n

Serial number

Unique for each UPS

o

Nominal Output Voltage

The Nominal Output Voltage
when running on batteries.

De-

fault “115” or “230” in Europe.