APC UPS control system User Manual
Page 191

X
Results of last self test
“OK” - good battery, “BT” -
failed due to insufficient capac-
ity, “NG” - failed due to overload,
“NO” - no results available (no
test performed in last 5 minutes)
Y
Enter smart mode
“SM”
Z—Z
Shutdown immediately (no delay)
- need > 1.5s between first and sec-
ond Z
N/A
a
Show protocol version.alert mes-
sages.valid commands (delimited
by periods)
“3.!$%+?=#—.ˆAˆNˆZ+-
789<@ABCDEFGKLMNOPQRSUVWXYZ’abcefgjklmnopqrsuvzy˜ˆ?”
-
Link-Level.alert-
messages.commands
b
Firmware revision
“50.9.D” - 50 = SKU (vari-
able
length),
9
=
firmware
revision,
D
=
country
code
(D=USA,
I=International,
A=Asia, J=Japan, M=Canada)
c
UPS local id
UPS IDEN (you can program any
8 characters here)
e
Return threshold
% battery charge threshold for re-
turn (00=00%, 01=15%, 02=25%,
03=90%)
f
Battery level %
Ranges - typical “100.0” when
fully charged as should normally
be the case
g
Nominal battery voltage (not ac-
tual voltage - see B)
“012” or “024” or “048”.
h
Measure-UPS: ambient humidity
(%)
“nnn.n” - percentage
i
Measure-UPS: dry contacts
10 = contact 1, 20 = 2, 40 = 3, 80
= 4
j
Estimated runtime at current load
(minutes)
“0112:”
(note, it is terminated
with a colon)
k
Alarm delay
0(zero) = 5 second delay after fail,
T = 30 second delay, L = alarm at
low battery only, N = no alarm
l
Low transfer voltage
Default “103” or “208” in Europe
m
Manufacturing date
Unique within groups of UPSes
(production runs)
n
Serial number
Unique for each UPS
o
Nominal Output Voltage
The Nominal Output Voltage
when running on batteries.
De-
fault “115” or “230” in Europe.
190