Dip switch info, Status bits, Ups status bits – APC UPS control system User Manual

Page 194

Advertising
background image

Dip switch info

Bit

Switch

Option when bit=1

0

4

Low battery alarm changed from 2 to 5 mins. Autostartup
disabled on SU370ci and 400

1

3

Audible alarm delayed 30 seconds

2

2

Output transfer set to 115 VAC (from 120 VAC) or to 240
VAC (from 230 VAC)

3

1

UPS desensitized - input voltage range expanded

4-7

-

Unused at this time

Status bits

This is probably the most important register of the UPS, which indicates
the overall UPS status. Some common things you’ll see:

• 08 = On line, battery OK

• 10 = On battery, battery OK

• 50 = On battery, battery low

• SM = Status bit is still not available (retry reading)

Bit

Hex
Bit

Meaning

0

0x01

1 = Runtime calibration occurring Not reported by Smart
UPS v/s and BackUPS Pro

1

0x02

1 = SmartTrim Not reported by 1st and 2nd generation Smar-
tUPS models

2

0x04

1 = SmartBoost

3

0x08

1 = On line (this is the normal condition)

4

0x10

1 = On battery

5

0x20

1 = Overloaded output

6

0x40

1 = Battery low

7

0x80

1 = Replace battery