p

Shutdown grace delay, seconds

Default “020” (020/180/300/600)

q

Low battery warning, minutes

Default “02”

r

Wakeup delay (time) - seconds

Default “000” (000/060/180/300)

s

Sensitivity

“H” - highest, “M” - medium, “L”
- lowest, “A” - autoadjust (Matrix
only)

u

Upper transfer voltage

Default “132” or “253” in Europe

t

Measure-UPS: ambient tempera-
ture (degrees C)

“nn.nn”

x

Last battery change

Eight characters. Varies typically
dd/mm/yy - 31/12/99

y

Copyright notice

“(C) APCC” - only works if
firmware letter (from “V”) is later
than O

z

Reset the EEPROM to factory
settings (but not ident or batt
replacement date) Not on Smar-
tUPS v/s or BackUPS Pro

“CLEAR”

+

Capability cycle

Cycle forward through possible
values (“—” from UPS afterward
to confirm change). Do not use
this unless you know how to pro-
gram your UPS EEPROM or you
may damage your UPS.

-

Capability cycle

Cycle backward through possible
values (“—” from UPS afterward
to confirm change)Do not use this
unless you know how to program
your UPS EEPROM or you may
damage your UPS.

@nnn

Shutdown (after delay ’p’) with
delayed wakeup of nnn tenths of
an hour (after ’r’ time)

Matrix/3rd gen UPS: “OK”, oth-
ers “*”

0x7f
(DEL
key)

Abort shutdown - use to abort @,
S, K—K

“OK”

˜

Register #1

See below

Register #2

See below

0

Battery constant

Set to A0 on SmartUPS 1000 with
new battery

4

???

Prints 35 on SmartUPS 1000

5

???

Prints EF on SmartUPS 1000

6

???

Prints F9 on SmartUPS 1000