Prior to installation – Siemens LB75564 User Manual

Page 16

Advertising
background image

Extractor hoods with 150 mm Ø air
outlet:
150 mm l extraction pipe

q

Screw the reducing connector (see

optional accessories on the last page)

onto the air outlet.

q

Attach the extraction pipe to the redu-

cing connector.

150 mm l extraction pipe

q

Attach the exhaust-air pipe directly to

the air outlet..

If a one-way flap has been fitted, con-

duct a performance test.
Extractor hoods with rectangular air
outlet:

q

Screw the enclosed
air-pipe connector
over the air outlet.

Recirculated air mode

q

The air cleaned by

an additional

activated carbon

filter is conveyed

back into the

room.

q

In recirculated air

mode the exhaust

opening must be

protected by a

grille (see optional accessories on the

last page) in order to prevent a mechani-

cal or electrical hazard.

Exhaust-air mode

Attaching the one-way flap

q

Insert the two lugs on the one-way flap

into the holes on the air-pipe connector

or air outlet and lock into position.

Before installing the one-way flap, ensu-

re that the lettering or stamp is on the out-

side.

Optimum performance of the extractor
hood:
q

Short, smooth extraction pipe.

q

As few pipe bends as possible.

q

Largest possible pipe diameter (prefera-

bly 150 mm ø) and large pipe bends.

q Round pipes:

We recommend
for single-motor model,

inner diameter of at least 120 mm
for double-motor model.

inner diameter of at least 150 mm

q Flat ducts must have an inner cross-

section equivalent to round pipes
which have an inner diameter of
120/150 mm.

120 mm l approx. 113 cm

2

150 mm l approx. 177 cm

2

q If pipe diameters differ: use sealing

strip.

q

Ensure an adequate air supply for
exhaust-air mode.

Pipe connection

Extractor hoods with 120 mm Ø air
outlet:
100 mm Ø extraction pipe

q

Insert the reducing connector (see optio-

nal accessories on the last page) into the

air-pipe connector and then attach the

exhaust-air pipe.

120 mm Ø extraction pipe

q

Attach the exhaust-air pipe directly to

the air-pipe connector.

Prior to installation

16

The exhaust air is discharged upwards

through a ventilation shaft or directly

through the outside wall into the open.

D

Exhaust air should neither be directed

into a smoke or exhaust flue that is

currently used for other purposes, nor into a

shaft that is used for ventilating rooms in

which stoves or fireplaces are also located.
Local authority regulations must be

observed when discharging air into smoke

or exhaust flues that are not otherwise in

use.

D

When the extractor hood is operated

in exhaust-air mode simultaneously with
a different burner which also makes use
of the same chimney (such as gas, oil or

coal-fired heaters, continuous-flow heaters,

hot-water boilers) care must be taken to
ensure that there is an adequate supply
of fresh air which will be needed by the

burner for combustion.
Safe operation is possible provided that the

underpressure in the room where the

burner is installed does not exceed 4 Pa

(0.04 mbar).
This can be achieved if the combustion air

can be replenished by being able to flow

through non-closeable openings such as in

doors, windows, wall ventilation boxes, or

by alternative technical measures such as

reciprocally shutting the other device off,

etc.
An air-intake/exhaust-air wall box by itself is

no guarantee that the limiting value will not

be exceeded.
Note: When assessing the overall

requirement, the combined ventilation

system for the entire household must be

taken into consideration. This rule does not

apply to the use of cooking appliances,

such as hobs and ovens.
All legal requirements concerning the

discharge of exhaust air must be observed.
Unrestricted operation is possible if the

extractor hood is used in recirculating mode

– with activated carbon filter.
The extractor hood should be fitted with a

one-way flap for exhaust-air mode if there is

not already one installed in the exhaust-air

pipe or wall box. If a one-way flap is not

enclosed with the appliance, purchase one

from a specialist outlet (see optional acces-

sories on the last page).

Advertising
This manual is related to the following products: