Aalborg DFC Digital User Manual

Page 34

Advertising
background image

APPENDIX 4

SENDING COMMANDS TO THE DFC

RS485

The standard DFC comes with an RS485 interface. The protocol described below
allows for the unit using either a custom software program or a “dumb terminal”.
All values are sent as printable ASCII characters. The start character is always !and
the command string is terminated with a carriage return (line feeds are
automatically stripped out by the DFC:

!<Addr>, <Cmd>,Arg1,Arg2,Arg3,Arg4<CR>

WHERE:

!

Start character

Addr

RS485 device address in the ASCII representation of
hexadecimal (00 through FF are valid).**

Cmd

The one or two character command from the table above.

Arg1 to Arg4

The command arguments from the table above.
Multiple arguments are comma delimited.

CR

Carriage return character.

**

Default address for all units is 11.

Several examples of commands follow.
All assume that the DFC has been configured for address 15 (0F hex) on the RS485 bus:

1.

To put the unit in digital mode:

!0F,M,D<CR>

The DFC will reply:

!0FMD<CR>

2.

To set the flow of 50% of FS:

!0F,S,50.0<CR>

The DFC will reply:

!0FS50.0<CR>

3.

To get a flow reading:

!0F,F<CR>

The DFC will reply:

!0F50.0<CR>
(Assuming the flow is at 50% FS)

4.

Set the high alarm limit to 5% above Set point:

!0F,A,H,5.0<CR>

The DFC will reply:

!0FA5.0<CR>

31

Advertising