6.8.2

EGD Example 1 – Configuring Node 2


To configure Node 2 for EGD Example 1, as shown in Figure 6.6, perform the following six steps:

1. On the main Cscape screen, select New on the File menu to start a new user program. Then

open the Ethernet Module Configuration dialog (Chapter 3, Figure 3.5 [page 18]), and fill in
the parameters for Node 2, as shown in Figure 6.14 below.

In this example, Node 2 will have a Static IP Address (Section 3.3.1 [page 21]), and the %R1,
%R2 and %R3 registers will be used to report the Ethernet Module’s status, firmware version,
and IP Address (step 5 in Section 3.1 [page 18]). Note that since an IP Address is 32-bits
long, Node 2’s IP Address (192.168.0.2) will actually be written into %R3 and %R4.

Figure 6.14- Ethernet Module Configuration - Node 2


2.
Click on the Config button next to the EGD (Ethernet Global Data) checkbox to open the

Ethernet Global Data Configuration dialog (Figure 6.1 [page 32]) and click on the Add Exch
button to create a Produced Exchange. Then, fill in the parameters for Node 2, as shown in
Figure 6.15 below, and click OK.

In this example, Node 2 will transmit Exchange 2 to a specific Consumer (Node 1), instead of
to a Group of Consumers. Also, the Production Period is set to 200, which will cause Node 2
to transmit Exchange 2 every 200 mS.