1 srtp overview, 2 srtp configuration, Srtp overview – Horner APG XL4 OCS HE-ETN300 User Manual

Page 57: Srtp configuration

Advertising
background image

SUP0740-07

CH.7

11/30/2009

Page 57 of 98

# 958

CHAPTER 7: SERVICE REQUEST TRANSFER PROTOCOL (SRTP)

7.1

SRTP Overview


Service Request Transfer Protocol (SRTP) is a GE Fanuc Automation protocol, which allows a
remote SRTP Client to request services from an SRTP Server. In this context, the Ethernet
Module acts as an SRTP Server, which responds to requests from one or more SRTP Clients.

Since SRTP was originally designed to support services provided by GE Fanuc Series 90 PLC
products, the Ethernet Module’s SRTP protocol, for OCS and RCS products, does not support all
possible SRTP services. The Ethernet Module’s implementation of SRTP is mainly limited to
those services required for the exchange of PLC register data.

The following SRTP service requests are supported by the Ethernet Module:

Request Code

Service Name

0 PLC_SSTAT
1 PLC_LSTAT
4 READ_SMEM
7 WRITE_SMEM

33 CHG_PRIV_LEVEL
67 RET_CONFIG_INFO
79 SESSION_CONTROL
97 PLC_FEATURES_SUPP

The READ_SMEM and WRITE_SMEM requests are supported for the following register types:

Selector

Register

Type

8 %R 16

bit

10 %AI 16

bit

12 %AQ 16

bit

16 %I 8

bit

18 %Q 8

bit

20 %T 8

bit

22 %M 8

bit

30 %S 8

bit

70 %I 1

bit

72 %Q 1

bit

74 %T 1

bit

76 %M 1

bit

84 %S 1

bit

7.2 SRTP

Configuration


If SRTP protocol will be used in the application, the general Ethernet Module Configuration,
previously described in Chapter 3, must be performed, and SRTP must be enabled. To enable
SRTP protocol, use Cscape Programming Software, to perform the following two steps:

1. Open the Ethernet Module Configuration dialog (Figure 3.5 [page 18]) as described in

Chapter 3.

Advertising
This manual is related to the following products: