13.4 Receiving ASCII characters from the client


In above configuration dialog %R500 register is used for receiving data. The receive data register
format will be as below.

Sl.No

Register Address

Data Content

1

%R500

First Register contains number of byes (characters)
received.

2

%R501

User can provide valid termination character here (if any). If
there is no termination character set this register value to
zero.

3

%R502

Received data. Each Register can hold 2 bytes of data.

4 %R503

Received

data.

..

Received

data.

..

Received

data.

n %R(500+n-1) Received

data.


Note: Maximum 2K ASCII characters can be received in a single request.

13.5 Status Information


%
R700 register is used for to display status information. Details of Status Register as below.

Bit No.

Description

1

Receive Data Overflow: Set when number received characters are more than
255.

2

Transmit Data Overflow: Set when transmit character count is more than 255.

3

Socket Creation Error: Set if there is any error in Socket creation.

4

Socket Allocate Error: Set if there is any internal memory allocation error for
transmitting data.

5

Socket Send Error: If error in transmitting TCP packet.

6 Reserved
7 Reserved
8 Reserved
9 Reserved
10 Reserved
11 Reserved
12 Reserved
13 Reserved
14 Reserved
15 Reserved
16

Receive Data indication Bit: Set when new packet is received. User can reset
this bit to ‘0’.