3 datalogger wiring (direct connection), Datalogger wiring (direct connection), 2. ground lug and power connectors on the avw200 – Campbell Scientific AVW200-series Vibrating Wire Interfaces User Manual
Page 28: 1. datalogger to avw200 cable options, N 4.3, N table 4-1

AVW200-series 2-Channel Vibrating Wire Spectrum Analyzer Modules
FIGURE 4-2. Ground Lug and Power Connectors on the AVW200
4.3 Datalogger Wiring (Direct Connection)
There are three options for connecting the AVW200 directly to the datalogger
(see TABLE 4-1); the cable is ordered as a common accessory.
TABLE 4-1. Datalogger to AVW200 Cable Options
Communication
Protocol
Cable Used
Datalogger Port for Cable Attachment
AVW200
Port for
Cable
Attachment
CR800,
CR850
CR1000,
CR3000
CR5000 CR10X CR23X
PakBus (direct
RS-232
connection)
18663 Null
Modem Cable
RS-232
RS-232
N/A
N/A
N/A
RS-232
PakBus (direct
RS-232
connection)
17855 or
SC110’s DTE
Cable (pigtail to
DB9; see
Control
port pair
(C1/C2
or
C3/C4)
Control
port pair
(C1/C2,
C3/C4,
C5/C6, or
C7/C8)
N/A
N/A
N/A
RS-232
SDI-12
CABLE3CBL-L
Cable
C1 or
C3
and G
C1, C3,
C5,
or C7
and G
SDI12
and
G
C1
through
C8 and
G
C5
through
C8 and
G
C1 and G
Connects to a power source via
19246 power cable
Connects to earth ground via an 8 AWG wire
when not directly connected to a datalogger
Indicates AVW200 is
connected to a power source
20