8. Troubleshooting Communication Problems

8.1 Unable to Communicate with DevConfig or Terminal

Emulator

If you are unable to communicate with DevConfig or the Terminal Emulator,

verify that:

(1) The AVW200 is powered. The red LED at the front of the AVW200 will

remain lit for 15 seconds on initial power up and then blink intermittently.

(2) The correct COM port has been selected. The COM port entry is provided

on the lower left corner of the DevConfig screen.

(3) The correct baud rate of the AVW200 has been selected. The default baud

rate of the AVW200 is 38400.

8.2 Datalogger to AVW200 Communication

If the datalogger fails to communicate with the AVW200, verify that:

(1) The AVW200 is powered. The red LED at the front of the AVW200 will

remain lit for 15 seconds on initial power up and then blink intermittently.

(2) The AVW200 PakBus address is different than the PakBus address of the

datalogger.

(3) The AVW200 PakBus address is entered correctly in the AVW instruction

of the datalogger program.

8.3 Wireless Communications

If you can’t connect, check out these possible causes:

1. Verify that the AVW20X is powered. The red LED at the front of the

AVW will remain lit for 15 seconds on initial power up and then blink

intermittently.

2. Active Interface set wrong

The active interface on the radio attached to the DL running the AVW

instruction must match the ComPort specified in the AVW instruction;

e.g., if you are using an RF401 (configured for SDC7) attached to a

datalogger to communicate with a remote AVW206, then the ComPort

specified in the AVW instruction must be SDC7 (or whatever active

interface the RF401 is set for).

3. Low or weak battery voltage or 12 VDC supply voltage

The power supply battery may not be charging properly due to solar panel

orientation, poor connection, or due to a charging transformer problem.

The battery itself may have discharged too low too many times, ruining

the battery. Lead acid batteries like to be topped off.

54