Campbell Scientific CR23X Micrologger User Manual
Page 30

CR23X MICROLOGGER OVERVIEW
OV-20
09: P74
Minimize instruction
01:1
One
repetition
02:10
Output the time of the daily minimum in hours
and minutes
03:2
Data source is Input Storage Location 2.
The program to make the measurements and to send the desired data to Final Storage has
been entered. At this point, Instruction 96 is entered to enable data transfer from Final Storage
to Storage Module.
10:P96
Activate Serial Data Output.
1:71
Output Final Storage data to Storage Module.
The program is complete. (Here the example reverts back to the key by key format.)
Key Display Explanation
∗
5
00:21:32 Enter
∗
5
Mode. Clock running but perhaps not set
correctly.
A
05:0000
Advance to location for year.
1
9
9
6
05:1996
Key in year (1996).
A
05:0000
Enter and advance to location for Julian day.
1
9
7
05:197
Key in Julian day.
A
05:0021
Enter and advance to location for hours and minutes (24 hr. time).
1
3
2
4
05:1324
Key in hrs.:min. (1:24 PM in this example).
A
:13:24:01
Clock set and running.
∗
0
Running Table 1 Exit
∗
5
, compile Table 1, commence logging data.