The event codes are defined in the table below.

# Description

Notes

0 no record

-

1 aux power unconfig auxiliary power module present but unconfigured.

2 aux power corrected auxiliary power module replaced after being missing.

3 aux power missing auxiliary power module not present but configured.

4 ac1 power restored ac for main board input restored.

5 ac1 power trouble

ac for main board input missing/brownout.

6 ac2 power restored ac for power module input restored.

7 ac2 power trouble

ac for power module input missing/brownout.

8 batttery1 restored

battery for main board input restored.

9 batttery1 trouble

battery for main board input missing.

10 battery2 restored

battery for power module input restored.

11 battery2 trouble

battery for power module input missing.

12 aud1 trb restored

audible #1 restored.

13 aud1 open trouble audible #1 open circuit.

14 aud1 short trouble

audible #1 short circuit.

15 aud2 trb restored

audible #2 restored.

16 aud2 open trouble audible #2 open circuit.

17 aud2 short trouble

audible #2 short circuit.

18 gnd fault restored

ground fault trouble restored to normal.

19 gnd fault present

ground fault present.

20 device present

addr device trouble: device returns canceling missing trouble

21 device missing

addr device trouble: device was polled but not found

22 commun restored addr device trouble: communication to device has returned to normal

23 bad communication addr device trouble: communication to device has errors (parity checksum etc.)

24 restored multiple

addr device trouble: multiple devices trouble has cleared

25 multiple devices

addr device trouble: multiple devices detected at this address

26 restored device kind addr device trouble: correct kind of device has been restored to this address

27 wrong device kind

addr device trouble: wrong kind of devices has been found

28 contaminated device addr device trouble: analog device is contaminated

29 loop module restored loop mod missing trouble has cleared

30 loop module missing loop module not in place but there are configured devices on the loops.

31 config menu accessed trouble stored when the configuration menu has been entered

32 factory initialized

history stored when a factory initialization has been invoked

33 uart failure

history stored when the uart has been corrupted by esd and then re-initialized.

34 uart restored

history stored when preceding trouble has cleared.

35 system reset

complete reset including power-down of loops for ten seconds.

36 trouble restored

trouble function input restore.

37 trouble input active

trouble function input present.

38 process restored

process control function input restored.

39 process input active

process control function input present.

40 supervisory restored supervisory function input restore.

41 supervisory active

supervisory function input present.