Data array parameters – Sierra Monitor Company FS-8700-48 User Manual

Page 9

Advertising
background image

FS-8700-48 Fike Cheetah Manual

Page 10 of 37

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

4

DATA ARRAY PARAMETERS

Data Arrays are “protocol neutral” data buffers for storage of data to be passed between protocols. It is necessary
to declare the data format of each of the Data Arrays to facilitate correct storage of the relevant data.

Section Title
Data_Arrays
Column Title

Function

Legal Values

Data_Array_Name

Provide name for Data Array

Up to 15 alphanumeric characters

Data_Array_Format

Provide data format. Each Data Array can only
take on one format. The Cheetah driver always
sets Data Array elements to a zero or one. Thus,
the use of bit arrays is suggested but is not
mandatory.

Float, BIT, UInt16, SInt16, Byte.

Data_Array_Length

Number of Data Objects. Must be larger than
the data storage area required by the Map
Descriptors for the data being placed in this
array.

1-10,000. If you use the 'All' keyword
when

setting

the

parameter

Cheet_Zone/Device then the minimum
length is 128.


Example

// Data Arrays

Data_Arrays

Data_Array_Name , Data_Array_Format , Data_Array_Length
ZONE_ALARMS

, Bit

, 256

PANEL_DATA

, Float

, 1000

DA_HIST

, Float

, 1000

DEVICE_L1_STATE

, Float

, 256

Advertising