FS-8700-48 Fike Cheetah Manual

Page 33 of 37

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

# Description

Notes

84 network silence

history stored when a silence command is recorded from cheetah net

85 network drill presnt

drill state activated from network - all zone only.

86 abort restored

abort state for this zone de-activated.

87 abort present

abort state for this zone activated.

88 pre-alarm1 restored pre-alarm 1 state for this zone de-activated.

89 pre-alarm1 present pre-alarm 1 state for this zone activated.

90 pre-alarm2 restored pre-alarm 2 state for this zone de-activated.

91 pre-alarm2 present pre-alarm 2 state for this zone activated.

92 network drill restor

drill state restored from network - all zone only.

93 alarm present

alarm state for this zone activated.

94 periph #aa missing

peripheral device of id#aa is missing.

95 pre-discharge

pre-discharge state for this zone activated.

96 periph #aa return

peripheral device of id#aa has returned on line.

97 release

release state for this zone activated.

98 zone enabled

zone disable state for this zone de-activated.

99 zone disabled

zone disable state for this zone activated.

100 watermist inactive

not used since release state never clears

101 watermist active

watermist state for this zone activated

102 network alarm unsil network command - unsilence alarms

103 network superv unsil network command - unsilence supervisories

104 checksum ok -----

zone configuration checksum error restored. zone number appended to this
message.

105 checksum error -----

zone configuration checksum error. zone number appended to this message.

106 network troubl unsil network command - unsilence troubles

107 vesda not configured trouble event stored when the hli is present but no vesda is configured.

108 vesda configur clear

trouble clear event for the above trouble.

109 config menu exited trouble clear event when the configuration menu has been exited

110 aux1 power restored auxiliary power input trouble restored - main board

111 aux1 power trouble auxiliary power input trouble - main board

112 aux2 power restored auxiliary power input trouble restored - power module

113 aux2 power trouble auxiliary power input trouble - power module

114 aud switch disabled enable/disable switch for audibles is in the disable position

115 aud switch restored enable/disable switch for audibles has returned to the enable position

116 diagnostics entered indicates the operator has accessed the diagnostic menu selections

117 zone disable restore frcm assigned to zone disable function has cleared

118 zone disable active

frcm assigned to zone disable function has activated

119 internal fault

device trouble from the 0x08 polling command

120 int fault restored

trouble restored from the 0x08 polling command

121 wiring fault-open

open circuit fault on supervised circuit: frcm/som/srm

122 wiring fault-short

short circuit fault on frcm/som/srm

123 acknowledge switch acknowledge switch pressed.

124 test point bad

analog device fire test point is out of hochiki specified range.

125 calibration restored

calibration fault has been restored. device now has valid calibration data.