(2) Removing the corner cover and

indicator cover

a) While lightly pressing the cen-

ter of the corner cover, pull up
the tab for the screw hole.
Use the same procedure to
remove the indicator cover.
(Fig. 6-16)

3-6-2. Installing the Ceiling Panel

(1) Hang the temporary latches on the inside of the ceil-

ing panel to the receptacle on the unit to temporarily
attach the ceiling panel in place. (Fig. 6-17)



The ceiling panel must be installed in the correct
direction relative to the unit. Align the REF. PIPE and
DRAIN marks on the ceiling panel corner with the
correct positions on the unit.

(2) Align the panel installation holes and the unit screw

holes. (Fig. 6-18)

(3) Tighten the supplied special screws at the 4 panel

installation locations so that the panel is attached
tightly to the unit.



Check that the wiring connectors are not caught
between the unit and the ceiling panel.

(4) Check that the panel is attached tightly to the ceiling.

(Fig. 6-19)



At this time, make sure that there are no gaps
between the unit and the ceiling panel, or between
the ceiling panel and the ceiling surface.



If there is a gap between the panel and the ceiling,
leave the ceiling panel attached and make fine
adjustments to the installation height of the unit to
eliminate the gap with the ceiling.

CAUTION

Fig. 6-17

Fig. 6-18

Fig. 6-19

Corner cover

Indicator cover

Press

Pull up

2

1

latch

Temporary latches

Temporary

DRAIN mark

Ceiling panel

Special screws

Refrigerant tubing joint

Drainage check

REF.PIPE mark

Panel installation hole
(4 locations)

Indoor unit

Ceiling panel

Ceiling surface

Do not allo

w

gaps

Adjust so that there are no gaps.

Air leakage

Air leakage from

ceiling surface

Staining

Condensation, water leakage

If the screws are not sufficiently tightened,
trouble such as that shown in the figure

the screws securely.

below may occur. Be sure to tighten

If a gap remains between the ceiling
surface and the ceiling panel even

adjust the height of the unit again.

after the screws are tightened,

The height of the unit can be adjusted from the ceiling
panel corner hole, with the ceiling panel attached, to

the drain hose, or other elements.

an extent that does not affect the unit levelness,

Fig. 6-16

Fig. 6-20