7

Hole-in-anchor

Concrete

Insert

Suspension bolt (M10 or 3/8")

Hole-in-plug

(locally purchased)

Fig. 6-1

23-5/8"(600mm)

21-1/32"(534mm)

Ceiling opening dimensions

Suspension bolt pitch

23-5/8"(600

mm

)

21-1/32"(534

mm

)

Ceiling opening dimensions

Suspension bolt pitch

Drain tube
connection port

22-5/8"(575mm)

6-11/16"

(170mm)

(160mm)

(53mm)

6-5/16"

2-3/32"

(45

mm

)

1-25/32"

(45

mm

)

1-25/32"

(117

mm

)

4-19/32"

Refrigerant tubing joint
(narrow tube side)

Power supply port

1-3/16"

(30

mm

)

(215

mm

)

8-15/32"

11-5/32"(283

mm

)

(outer dia 1-1/32"( 26mm))

1/4( 6.35mm) (flared)

1/2" – 23/32" (13~18

mm

)

Over 19/32" (15

mm

)

Supplied screw

Full-scale installation diagram
(printed on top of container box)

3. How to Install the Indoor Unit

3-1. Preparation for Suspending
This unit uses a drain pump. Use a carpenter’s level to
check that the unit is level.

3-2. Suspending the Indoor Unit

(1) Fix the suspension bolts securely in the ceiling using

the method shown in the diagrams, by attaching
them to the ceiling support structure, or by any other
method that ensures that the unit will be securely
and safely suspended. (Fig. 6-1)

(2) Follow the diagram to make the holes in the ceiling.

(3) Determine the pitch of the suspension bolts using

the supplied full-scale installation diagram. The dia-
gram shows the relationship between the positions
of the suspension fitting, unit, and panel. (Fig. 6-2)

3-3. Placing the Unit Inside the Ceiling

(1) Be sure to remove the fan protection (4pcs) for

transportation before hanging up the indoor unit.

(2) When placing the unit inside the ceiling, determine

the pitch of the suspension bolts using the supplied
full-scale installation diagram. (Fig. 6-3)
Tubing and wiring must be laid inside the ceiling
when suspending the unit. If the ceiling is already
constructed, lay the tubing and wiring into position
for connection to the unit before placing the unit
inside the ceiling.

(3) The length of suspension bolts must be appropriate

for a distance between the bottom of the bolt and the
bottom of the unit of more than 19/32" (15 mm) as
shown in the diagram. (Fig. 6-3)

(4) Thread the 3 hexagonal nuts (locally purchased) and

2 supplied washers onto each of the 4 suspension
bolts as shown in the diagram. Use 1 nut and 1
washer for the upper side, and 2 nuts and 1 washer
for the lower side, so that the unit will not fall off the
suspension lugs. (Fig. 6-4)

(5) Adjust so that the distance between the unit and the

ceiling bottom is 1/2" (13 mm) to 23/32" (18 mm).
Tighten the nuts on the upper side and lower side of
the suspension lug. (Fig. 6-4)

Nuts and washers
(used for upper and lower)

Double nut

Notch

Suspension lug

Suspension bolt

1/2" – 23/32"

(13~18mm)

Fig. 6-4

Fig. 6-2

Fig. 6-3