Specifications, Ordering information, Safety information – NOVUS Controller N3000 User Manual

Page 11: Support and maintenance, Limited warranty and limitation of liability

Advertising
background image

Controller N3000

NOVUS AUTOMATION

11/11

The RS-485 signals are:

D1 D D + B

Bidirectional data line

Terminal 25

D0

D:

D - A

Inverted bidirectional data line

.

Terminal 26

C

Ground. Optional connection to

improve communication

performance

Terminal 27

GND

COMMUNICATION PARAMETERS CONFIGURATION
Two parameters must be configured for serial use:

bavd

: Communication speed. All equipments with the same speed.

prty

:

Parity of the communication.

Addr

: Controller communication address. Each controller must

have an exclusive address.

SPECIFICATIONS

DIMENSIONS: ............................................ 96 x 96 x 92 mm (1/4 DIN)

.................................................................... Approximate weigth: 350 g
PANEL CUT-OUT: .................................... 93 x 93 mm (+0.5 -0.0 mm)
POWER: ................................... 100 to 240 Vac/dc (±10 %), 50/60 Hz.

Transient overvoltage: ±2 kV

Optional 24 V: ................ 12 to 24 Vdc / 24 Vac (-10 % / +20 %)

Max. Consumption: ........................................................... 9 VA

ENVIRONMENTAL CONDITIONS: ....................................... 5 to 50 °C

.............................. Relative humidity (maximum): 80 % up to 30 ºC.

...................... For temperatures above 30 ºC, decrease 3 % per ºC.

Installation category II. Pollution degree 2. Altitude < 2000 m

INPUT .................... Keyboard selection of input type (refer to Table 1)

Internal resolution: .................................................. 32767 levels

Display resolution: .................12000 levels (from -1999 to 9999)

Input sample rate: .................................................. 10 per second
Accuracy: ....... Thermocouples J, K and T: 0.25 % of span ±1 ºC
................. Thermocouple E, N, R, S and B: 0.25 % of span ±3 ºC

...................................................................... Pt100: 0.2 % of span

................................... 4-20 mA, 0-50 mV, 0-5 Vdc: 0.2 % of span.
Input impedance: . 0-50 mV, Pt100 and thermocouples: >10 MΩ
.................................................................... 0-5 V / 0-10 V: >1 MΩ
................................................. 4-20 mA: 15 Ω (+2 Vdc @ 20 mA)
Pt100 measurement: ................................. standard (α=0.00385)

Excitation current: ................................. 0.170 mA. 3-wire circuit,

cable resistance compensation
All input types are factory calibrated according to IEC-584 for

thermocouples and IEC-751 for Pt100.

DIGITAL INPUT: ... I/O5 AND I/O6: Dry contact or NPN open collector
ANALOG OUTPUT: ............... I/O5: 0-20 mA or 4-20 mA, 550 Ω max.

.............................................................................. 1500 levels, Isolated

.................................... Control output or PV or SP retransmission

CONTROL OUTPUT: .. 2 Relays SPDT (I/O1 and I/O2): 3 A / 240 Vac

..................... 2 Relays SPST-NO (I/O3 and I/O4): 1.5 A / 250 Vac

...................... Logic pulse for SSR drive (I/O5): 10 V max / 20 mA
........................ Logic pulse for SSR drive (I/O6): 5 V max / 20 mA

SECOND ANALOG INPUT: ....... 4-20 mA remote set point (standard).
AUXILIARY POWER SUPPLY: ....................... 24 Vdc, ±10 %; 25 mA
FRONT PANEL: ................................... IP65, policarbonato UL94 V-2;
CASE
: ............................................................ IP30, ABS+PC UL94 V-0
ELECTROMAGNETIC COMPATIBILITY
: ............................................

.......................................... EN 61326-1:1997 and EN61326-1/A1:1998
EMISSION: .............................................................CISPR11/EN55011
IMMUNITY: ...................... EN61000-4-2, EN61000-4-3, EN61000-4-4,

EN61000-4-5, EN61000-4-6, EN61000-4-8 and EN61000-4-11
SECURITY: ...........................................................................................

.............. EN61010-1:1993 and EN61010-1/A2:1995 (UL file E300526)
USB INTERFACE: 2.0, CDC class (virtual communications port),

MODBUS RTU protocol.

SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6.3

mm;
PROGRAMMABLE PWM CYCLE FROM 0.5 SEC. AND 100 SEC;
START UP
: 3 seconds after power up.
CERTIFICATIONS
: ...................................... CE / UL (FILE: E300526)

ORDERING INFORMATION

N3000 -

485 -

24V

A

B

C

A: Model:

N3000;

B: Digital Communication: blank (basic version without serial

communication);

485 (RS485, Modbus protocol);

C: Power Supply:

blank (basic version, 100 to 240

Vac/dc);

24V (12 to 24 Vdc / 24 Vac input

voltage).

SAFETY INFORMATION

Any control system design should take into account that any part of the

system has the potential to fail. This product is not a protection or safety

device and its alarms are not intended to protect against product

failures. Independent safety devices should be always provided if

personnel or property are at risk.
Product performance and specifications may be affected by its

environment and installation. It’s user’s responsibility to assure proper

grounding, shielding, cable routing and electrical noise filtering, in

accordance with local regulations, EMC standards and good installation

practices.

SUPPORT AND MAINTENANCE

This product contains no serviceable parts inside. Contact our local

distributor in case you need authorized service. For troubleshooting,

visit our FAQ at www.novusautomation.com.

LIMITED WARRANTY AND LIMITATION OF

LIABILITY

NOVUS warrants to the original purchaser that this product is free from

defects in material and workmanship under normal use and service

within one (1) year from the date of shipment from factory or from its

official sales channel to the original purchaser.
NOVUS liability under this warranty shall not in any case exceed the

cost of correcting defects in the product or of supplying replacement

product as herein provided and upon the expiration of the warranty

period all such liability shall terminate.
For complete information on warranty and liability limitations, check

appropriate section in our web site: www.novusautomation.com.