The function to be used in each channel of I/O is defined by the user

in accordance with the options shown in the Table 2.

I/O FUNCTION

I/O TYPE

CODE

No function

-

OFF

Alarm 1 Output

Output

A1

Alarm 2 Output

Output

A2

Alarm 3 Output

Output

A3

Alarm 4 Output

Output

A4

LDB Output - Loop break detection

Output

Lbd

Control Output (Relay or Digital Pulse)

Output

CTRL

Automatic/Man mode change

Digital Input

mAN

Run/Stop mode change

Digital Input

RVN

Selected Remote SP

Digital Input

RSP

Freezes program execution

Digital Input

KPRG

Program 1 selection

Digital Input

PR 1

0 to 20 mA analog control output

Analog Output

(.0.20

4 to 20 mA analog control output

Analog Output

(.4.20

0 to 20 mA PV retransmission

Analog Output

P.0.20

4 to 20 mA PV retransmission

Analog Output

P.4.20

0 to 20 mA SP retransmission

Analog Output

S.0.20

4 to 20 mA SP retransmission

Analog Output

S.4.20

Table 2 - I/O channel functions

The description for the functions follows:
• OFF - No function.
The I/O channel programmed with code 0 will not be used by the

controller. It is available to be used by serial communication as digital

output.
• A1, A2, A3, A4 - Alarm output.
Available for all I/O channels. The selected channel can be used as

output to Alarms 1 to 4.
• Lbd – Loop Break Detector function.
Assigns the output of the Loop Break Detector alarm to an I/O

channel. Available to all I/O channels.

CTRL

- PWM control output.

Defines the channel to be used as control output (relay or digital

pulse). Available for all the channels. The digital pulse is available on

(when available) I/O5 and I/O6.
• mAN - Digital input with Auto/Manual function.
Defines the channel as Digital Input with the function of switching the

control mode between Automatic and Manual. Available for I/O5,

I/O6 and key

.

Closed: Manual control /no

Opened: Automatic control /YES

• RVN - Digital input - Standard for I/O5, I/O6 and key. Start/Stop

input (“rvn”: YES / no).

Closed: outputs enabled/ YES

Opened: outputs disabled/ no

• RSP - Digital input - Standard for I/O5, I/O6 and

key.

Closed: remote SP (4-20 mA in remote SP input)

Opened: main SP (internal programmed SV)

• KPRG - Digital input - Standard for I/O5, I/O6 and

key.

Opened: enables R&S program

Closed: holds R&S program (the program resumes when the contact

is opened again)

Closed Contact: Enables execution of the program

Opened Contact: Interrupts execution of the program

Note: Even when the execution of the program is interrupted,

the control output remains active and controlling the process at

the point (Setpoint) of interruption. The program will resume its

normal execution starting from this same point when the digital

input is closed.
• PR 1 - Digital input - Standard for I/O5, I/O6 and

key. Selects

R&S program 1. Used to alternate between the main Setpoint and

a second Setpoint defined by the R&S program 1.

Closed: selects program 1

Opened: uses main Setpoint

• (.0.20 / (.4.20 - 0-20 mA and 4-20 mA Control Output.

Available for I/O 5 only, defines the channel as a 0-20 mA and 4-20 mA

control output.
• P.0.20 / P.4.20- 0-20 mA and 4-20 mA PV retransmissions.

Available for I/O 5 only, configures the channel to retransmit the PV

measurement in 0-20 mA and 4-20 mA.
• S.0.20 / s.4.20- 0-20 mA and 4-20 mA SP (Setpoint)

retransmissions.

Available for I/O 5 only, configures the channel to retransmit the

values of SP in 0-20 mA and 4-20 mA.

ALARMS FUNCTIONS
The controller has 4 independent alarms. They can be programmed

to operate with eight different functions, represented in Table 3.
• off – Alarms turned off.
• ierr – Sensor break alarm
It is activated whenever the input sensor is broken or disconnected.
• rs – Ramp & soak program event alarm
This alarm is activated by the Ramp & Soak program (refer to the

PROGRAMS OF RAMP AND SOAK section on how to set the event

alarm).
• lo – Alarm of Absolute Minimum Value
It is activated when the measured value is below the value defined in

the alarm Setpoint.
• ki – Alarm of Absolute Maximum Value
It is activated when the measured value is above the value defined in

the alarm Setpoint.
• dif – Alarm of Differential Value
In this function, the parameters “SPA1”, “SPA2”,”SPA3” and “SPA4”

represent the PV deviation as compared to the main SP.
Using the Alarm 1 as example: for Positive SPA1 values, the

differential alarm will be triggered when the PV value is out of the

range defined in:

(SP –SPA1) to (SP + SPA1)

For a negative SPA1 value, the differential alarm will be triggered

when the PV value is within the range defined above
• difl – Alarm of Minimum Differential Value
It is activated when the PV value is below the value defined in:

(SP –SPA1)

Using the Alarm 1 as example.
• difk – Alarm of Maximum Differential Value
It is activated when the PV value is above the value defined in:

(SP + SPA1)

Using the Alarm 1 as example.