The initial blocking is useful, for example, when one of the alarms is

set up as a minimum value alarm, which may cause the activation of

the alarm soon upon the process start-up; an occurrence that may

undesirable in many cases.
The initial blocking is not valid for the function ierr (Sensor Break).
OFFSET
Allows the user to perform fine adjustments to the PV indication. It

allows the correction of measuring errors that appear, for example,

on the replacement of the temperature sensor.
RETRANSMISSION OF PV
The indicator may include an analog output which performs the

retransmission of the values of PV into a signal of 0-20 mA or 4-20

mA. The analog retransmission can be scaled, i.e., there are

minimum and maximum limits to establish the retransmission range,

defined in the parameters rtLLandrtkL.
The analog output is available on terminals 13 and 14 for models

N1040i-RA and N1040i-RA-485.
In order to obtain retransmission in electrical voltage, the user shall

install a shunt resistor (500 Ω max.) across the analog output

terminals. This resistor value depends on the desired voltage range.
The analog retransmission output is not electrically isolated from the

RS485 serial communication.
24 Vdc AUXILIARY VOLTAGE SOURCE
Another feature that may be available in the indicator is an auxiliary

power supply for exciting field transmitters (two-wire 4-20 mA

transmitters).
The 24 Vdc output is on terminals 13 and 14 for models N1040i-RE

and N1040i-RE-485.
The 24 V auxiliary power supply is not electrically isolated from the

RS485 serial communication.

INSTALLATION / CONNECTIONS

The indicator shall be fastened on a panel, following the sequence of

steps described below:
• Prepare a cut-out of 46 x 46 mm on the panel;
• Remove the mounting clamp from the indicator;
• Insert the indicator into the cut-out from the front side of the

panel;

• Place the clamp on the indicator again, pressing until firm grip to

the panel.

SAFETY ALERTS

The symbols below are used on the equipment and throughout this

manual in order to draw the user´s attention to important information

related to the equipment safety and operation.

CAUTION:

Read the manual thoroughly

before installing and operating

the equipment

CAUTION OR DANGER:

Electrical shock hazard

All safety related instructions that appear in the manual must be

observed to ensure personal safety and to prevent damage to either

the instrument or the system. If the instrument is used in a manner not

specified by the manufacturer, the protection provided by the

equipment may be impaired.

ELECTRICAL CONNECTIONS
The position of the features on the indicator back panel is shown on

Figure 01:

Figure 01 – Inputs connections and power supply

In the models with two alarms and serial communication, the

connections are:

Figure 02 - Alarms and serial communication connections

In the models with one alarm, retransmission of PV and serial

communication, the connections are:

Figure 03 - Alarm, retransmission and serial communication connections

In the models with one alarm, 24 Vdc auxiliary voltage source and

communication, the connections are:

Figure 04 - Alarm, auxiliary source and communication connections

A typical application of the auxiliary voltage source is to supply loop

power for field transmitters (two-wire 4-20 mA). Figure 05 shows the

necessary wiring for this application.

Figure 05 – Example for the use of the indicator auxiliary voltage source