1 recomendations for installation, 2 battery power supply, 1 replacing the internal battery – NOVUS RHT-Air User Manual

Page 3: 6 configuration / operation

Advertising
background image

RHT-Air

NOVUS AUTOMATION

3/8

Fig. 6 - Electrical wiring

RHT-Air is manufactured with the jumper (J1) set in the position “EXT”

for external power supply.

5.1.1 RECOMENDATIONS FOR INSTALLATION

• Conductors of small electric signals must be separated from activation

conductors or higher current or power in the system’s plan, if possible in

grounded electroducts.

• The instrument’s supply must come from a network proper for

instrumentation.

• In control and monitoring applications, it is essential to consider what

may happen when any part of the system fails.

• The use of RC FILTERS (47 Ω and 100 nF, series) in parallel with

contactor and solenoid coils, etc. is recommended.

5.2 BATTERY POWER SUPPLY

RHT-Air can be supplied by an internal battery whenever the equipment is

not energized by the electrical grid. Below are guidelines on how to proceed

for supplying power with a battery:

• Remove the four set screws of the front panel of the equipment RHT-Air,

taking the necessary precaution not to apply force on the internal connector

of the electronic circuit.

• After removing the front panel, change the position of the jumper (J1) to

“BAT” so that it can be supplied through the battery. Replace the front

panel, by placing the four set screws, taking the necessary precaution

not to apply force on the internal connector of the electronic circuit.

5.2.1 REPLACING THE INTERNAL BATTERY

It is possible to check the battery’s charge through register “29”. A fully charged

battery typically has a power above 3.6 V. As you use the RHT-Air, the power

of the battery will gradually decrease. It is recommended that you check the

value of registry “29" regularly so that when it reaches below 3.3 V, the battery

can be replaced.
Note: Even when the power is below 100 %, the equipment will operate

normally.

Only suitable replacement battery for this product is:

MANUFACTURER: OMNICELL

MODEL: ER14250HD

• Remove the four set screws of the front panel, taking the necessary

precaution not to apply force on the internal connector of the electronic

circuit. After removing the front panel, replace the battery, taking the

necessary precaution not to touch the electronic circuit.

• Insert a new battery and replace the front panel carefully, placing the

four molding screws.

6 CONFIGURATION / OPERATION

The application DigiConfig is a Windows® software used for configuring

RHT-Air. In order to install it, please run the file “DigiConfigSetup.exe” from

the CD that comes with the equipment and follow the instructions therein.
DigiConfig comes with an unabridged help tutorial, containing all the

necessary information for you to use it. If you want to use help tutorial, start

the application and select the "Help” menu or press "F1".
If you do not have the CD that comes with the equipment, go to

www.novusautomation.com to get the DigiConfig installer and the additional

manual guides.
Users will receive the fully calibrated adjustment-free equipment. The original

configuration is shown below:
Addr

(Communication address) = 246

Time (Update interval) = 60

Advertising