6 serial communication, 1 modbus commands, 2 description of some registers – NOVUS RHT-P10-485-LCD User Manual

Page 4

Advertising
background image

RHT-WM-485-LCD, RHT-DM-485-LCD and RHT-P10-485-LCD Transmitters

NOVUS AUTOMATION

4/6

Read-only screens of the values measured by the transmitter:

5ª Screen: Temperature

6ª Screen: Relative Humidity

7ª Screen: Dew Point

6 SERIAL COMMUNICATION

The transmitter is provided with RS485 serial communication, operating as a

slave within the Modbus RTU network. The configuration of the transmitter is

performed through the serial (RS485) interface. For configuring the
communication parameters you can use the programming

button.

In this section you will find the instructions necessary to perform the data

reading without using the DigiConfig software. In order to assure correct

configuration of the transmitter, always use the DigiConfig software. After

being configured, the input data may be accessed by any other software

capable for Modbus RTU communication.

6.1 MODBUS COMMANDS

The Modbus RTU commands (functions) listed in the table below are

implemented. For further information with respect to each of these

commands and the Modbus protocol in general, please access the site

www.modbus.org.

READ HOLDING REGISTERS – 0x03
This command can be used for reading the value of one or several holding

registers, according to the “Holding Registers Table”.

WRITE HOLDING REGISTERS – 0x06
This command can be used for writing in a holding register, according to the

“Holding Registers Table”.

6.2 DESCRIPTION OF SOME REGISTERS

REGISTER 2 – BAUD-RATE
Defines the Modbus communication speed. The transmitter comes factory-

configured with a Baud-Rate of 1200.

Code

Baud-rate

0

1.200

1

2.400

2

4.800

3

9.600

4

19.200

5

38.400

6

57.600

7

115.200

REGISTER 3 – MODBUS ADDRESS
Defines the address of the transmitter within the Modbus network. Values

between 1 and 247. The transmitter comes factory-configured with address

247.

REGISTER 4 – PARITY
Defines the parity code used for Modbus communication. The transmitter

comes factory-configured with parity even.

Code

Parity

0

None

1

Odd

2

Even