Operation – NOVUS N1040 Controller User Manual

Page 2

Advertising
background image

N1040 Controller

NOVUS AUTOMATION

2/5

ALARM OUTPUT
The controller contains 2 alarms that can be directed (assigned) to any
output channel. The alarm functions are described in Table 02.

off

Output is not used as alarm.

lo

Alarm of Absolute Minimum
Value. Triggers when the
value of measured PV is
below the value defined for
alarm Setpoint.

SPA1

PV

ki

Alarm of Absolute Maximum
Value. Triggers when the
value of measured PV is
above the value defined for
alarm Setpoint.

SPA1

PV

dif

Alarm of Differential Value. In this function the
parameters SPA1 and SPA2 represent the deviation
of PV in relation to the SP of CONTROL.

SP

PV

SP + SPA1

SP

– SPA1

SP

PV

SV

– SPA1

alarme

SV + SPA1

alarme

Positive SPA1

Negative SPA1

difl

Alarm of Minimum Differential Value. It triggers when
the value of PV is below the defined point by (using
the Alarm 1 as example).

SP

PV

SP

– SPA1

SP

PV

SP

– SPA1

Positive SPA1

Negative SPA1

difk

Alarm of Valor Maximum Differential Value. Triggers
when the value of PV is above the defined point by
(using Alarm 1 as example):

SP

PV

SP + SPA1

SP

PV

SP + SPA1

Positive SPA1

Negative SPA1

ierr

Sensor Break Alarm. Activated when the input signal
of PV is interrupted, out of the range limits or Pt100 in
short-circuit.

Table 02 – Alarm functions

Note: Alarm functions on Table 02 are also valid for Alarm 2 (SPA2).

INITIAL BLOCKING OF ALARM
The initial blocking option inhibits the alarm from being recognized
if an alarm condition is present when the controller is first energized
(or after a transition from run YES  NO). The alarm will be enabled
only after the occurrence of a non alarm condition followed by a new
occurrence for the alarm.
The initial blocking is useful, for instance, when one of the alarms is
configured as a minimum value alarm, causing the activation of the
alarm soon upon the process start-up, an occurrence that may be
undesirable.
The initial blocking is disabled for the sensor break alarm function.

OFFSET
Allows fine adjustments to the PV reading for compensation of
sensor error.

FUNÇÃO LBD – LOOP BREAK DETECTION
The parameter defines a time interval, in minutes, within which the
PV is expect to react to a control output signal. If the PV does not
react properly within the time interval configured in lbd.t, the
controller interprets this as a control loop break and signals this
occurrence in the display.
A LBD event may be sent to any output channel. Simply configure
the LDB function to the desired output channel (OUT1 or OUT2): the

selected output will be activated when a LDB condition is detected.
When the Lbd.t parameter is programmed with 0 (zero), the LDB
function is disabled.
The LBD is useful in detecting system failures, such us defective
sensors or actuators, loads and power supply, among others.

SAFE OUTPUT VALUE WITH SENSOR FAILURE
This function defines an output value (user defined) to be assigned to
the control output in the event of a sensor failure.
When the input sensor is identified as broken, the controller switches
the control mode to MANUAL while forcing MV to assume the user
configured value in the 1E.ov parameter. This function requires that
one of the alarms be configured as 1Err and the 1E.ov parameter
(control output percentage) programmed with a value other then 0
(zero).
Once this function is triggered, the controller remains in SAFE mode
(MANUAL control output) even after the sensor failure appears to be
fixed. The operator intervention is required for switching back to
AUTO mode.
1E.ov

values are only 0 and 100 % when in ON/OFF control mode.

For PID control mode any value in the range from 0 to 100 % is
accepted.

OPERATION

The controller’s front panel, with its parts, can be seen in the Fig. 02:

Fig. 02 - Identification of the parts referring to the front panel

Display of PV / Programming (top display, red color): Displays the
current value of PV (Process Variable). When in configuration mode,
it shows the parameters names.
Display of SP / Parameters (bottom display, green color): Displays
the value of SP (Setpoint). When in configuration mode, it shows the
parameters values.
TUNE Indicator: Stays ON while the controller is in tuning process.
OUT Indicator: For relay or pulse control output; it reflects the actual
state of the output.
A1 and A2 Indicators: signalize the occurrence of alarm situation.
P Key: used to walk through the menu parameters.

Increment key and

- Decrement key: allow altering the

values of the parameters.

Back key: used to retrocede parameters.

OPERATION
When the controller is powered up, it displays its firmware version for
3 seconds, after which the controller starts normal operation. The
value of PV and SP is then displayed and the outputs are enabled.
In order for the controller to operate properly in a process, its
parameters need to be configured first, such that it can perform
accordingly to the system requirements. The user must be aware of
the importance of each parameter and for each one determine a valid
condition.
The parameters are grouped in levels according to their functionality
and operation easiness. The 5 levels of parameters are:

1 – Operation / 2 – Tuning / 3 – Alarms / 4 – Input / 5 – Calibration

The “P” key is used for accessing the parameters within a level.
Keeping the “P” key pressed, at every 2 seconds the controller jumps
to the next level of parameters, showing the first parameter of each
level:

PV >> atvn >> fva1 >> type >> pass >> PV …

Advertising