NOVUS N1040 Controller User Manual

Page 5

Advertising
background image

N1040 Controller

NOVUS AUTOMATION

5/5

PART NUMBER FORMATION

N1040 – PR – F

Basic version; two outputs: OUT1= logical
pulse / OUT2= relay
- Wide input power range:

100 to 240 Vac

24 to 240 Vdc

N1040 – PRR

Three outputs: OUT1= logical pulse / OUT2
and OUT3 = relay

N1040 – PRRR

Four outputs: OUT1= logical pulse / OUT2,
OUT3 and OUT4= relay

SPECIFICATIONS

DIMENSIONS: ............................................................ 48 x 48 x 80 mm

Approximate:........................................................................... 75 g

POWER SUPPLY: ..........................100 to 240 Vac (±10 %), 50/60 Hz

................................................................... 48 to 240 Vdc (±10 %)

.............................. 24 to 240 Vdc (±10 %) for model N1040-PR-F

Maximum consumption: ......................................................... 6 VA

ENVIRONMENTAL CONDITIONS:

Operation Temperature: ............................................... 0 to 50 °C
Relative Humidity: ................................................... 80 % @ 30 °C
............... For temperatures above 30 °C, reduce 3 % for each °C
...... Internal use; Category of installation II, Degree of pollution 2;
altitude < 2000 meters

INPUT ...... Thermocouples J; K; T and Pt100 (according of Table 01)

Internal Resolution: ...................................... 32767 levels (15 bits)
Resolution of Display: ......... 12000 levels (from -1999 up to 9999)
Rate of input reading: .........................................up 55 per second
Precision: ....... Thermocouples J, K, T: 0.25 % of the span 1 °C
................................................................ Pt100: 0.2 % of the span
Input Impedance: .................. Pt100 and thermocouples: > 10 M
Measurement of Pt100: ......................... 3-wire type, ( =0.00385)
With compensation for cable length, excitation current of 0.170
mA.

OUT1: ......................................................... Voltage pulse, 5 V / 25 mA
OUT2: ....................................... Relay SPST; 1.5 A / 240 Vac / 30 Vdc
OUT3: ....................................... Relay SPST; 1.5 A / 240 Vac / 30 Vdc
OUT4: ..........................................Relay SPDT; 3 A / 240 Vac / 30 Vdc
FRONT PANEL: ......................... IP65, Polycarbonate (PC) UL94 V-2
ENCLOSURE
: .............................................. IP30, ABS+PC UL94 V-0
ELECTROMAGNETIC COMPATIBILITY: ............... EN 61326-1:1997
and EN 61326-1/A1:1998
EMISSION: ............................................................ CISPR11/EN55011
IMMUNITY: ...................... EN61000-4-2, EN61000-4-3, EN61000-4-4,
EN61000-4-5, EN61000-4-6, EN61000-4-8 and EN61000-4-11
SAFETY: .......................... EN61010-1:1993 and EN61010-1/A2:1995
SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS;
PROGRAMABLE CYCLE OF PWM DE 0.5 UP 100 SECONDS;
STARTS UP OPERATION AFTER 3 SECONDS CONNECTED TO
THE POWER SUPPLY.
CERTIFICATION:








SAFETY INFORMATION

Any control system design should take into account that any part of
the system has the potential to fail. This product is not a protection or
safety device and its alarms are not intended to protect against
product failures. Independent safety devices should be always
provided if personnel or property are at risk.
Product performance and specifications may be affected by its
environment and installation. It’s user’s responsibility to assure
proper grounding, shielding, cable routing and electrical noise
filtering, in accordance with local regulations, EMC standards and
good installation practices.

SUPPORT AND MAINTENANCE

This product contains no serviceable parts inside. Contact our local
distributor in case you need authorized service. For troubleshooting,
visit our FAQ at

www.novusautomation.com

.

LIMITED WARRANTY AND LIMITATION OF

LIABILITY

NOVUS warrants to the original purchaser that this product is free
from defects in material and workmanship under normal use and
service within one (1) year from the date of shipment from factory or
from its official sales channel to the original purchaser.
NOVUS liability under this warranty shall not in any case exceed the
cost of correcting defects in the product or of supplying replacement
product as herein provided and upon the expiration of the warranty
period all such liability shall terminate.
For complete information on warranty and liability limitations, check
appropriate section in our web site:

www.novusautomation.com

.