NOVUS N1100HC User Manual

Page 5

Advertising
background image

N1100HC Controller

NOVUS AUTOMATION

5/7

7.3

CONTROL # 2 PARAMETERS

Pb2

Pb2

Pb2

Pb2

PROPORTIONAL BAND: Percentage of maximum
input span. Select zero for ON/OFF control.

Olap

Olap

Olap

Olap

(overLAP): defines the overlap between the heat and cool
outputs. The overlap is given in engineering units of the
input type used.

When the overlap value is negative, it represents the value
of the dead-band instead.

If PB2=0, the overlap parameter is changed to represent
the hystesesis value for control #2.

[t2

[t2

[t2

[t2

CYCLE TIME: PWM period in seconds. Can only be
viewed if proportional band is other than zero.

A[t2

A[t2

A[t2

A[t2

CONTROL ACTION: For Auto Mode only.

Reverse Action

rE

rE

rE

rE

usually used for heating.

Direct Action

dir

dir

dir

dir

usually used for cooling.

O2ll

O2ll

O2ll

O2ll

OUTPUT LOW LIMIT: minimum percentage value for

MV (Manipulated Variable) when in automatic
control and PID. Default value: 0.0 %

O2kl

O2kl

O2kl

O2kl

OUTPUT HIGH LIMIT: Maximum percentage value

for MV when in automatic control and PID. Default
value: 100.0 %

7.4

RAMP AND SOAK PROFILE PROGRAMMING CYCLE

tbas

tbas

tbas

tbas

TIME BASE: Selects the time base for the ramp and
soak. Valid for all profile programs.

0

0

0

0

- PT1 to PT7 values are in seconds;

1

1

1

1 - PT1 to PT7 values are in minutes;

Pr n

Pr n

Pr n

Pr n

PROGRAM TO BE VIEWED: Selects the ramp and
soak profile program to be edited/viewed in the
following cycle prompts (7 programs available).

ptol

ptol

ptol

ptol

RAMP AND SOAK TOLERANCE: maximum
deviation between PV and SV. Whenever this
deviation is exceeded the time counter is halted until
deviation lowers to within the tolerance. Set zero to
disable this function.

Psp0

Psp0

Psp0

Psp0

Psp5

Psp5

Psp5

Psp5

RAMP AND SOAK SET POINTS (0 to 5): Set of 8 SV
values which define the ramp and soak profile
segments. See also

PT1

to

5

and

PE1

to

5

below.

Pt1

Pt1

Pt1

Pt1

Pt5

Pt5

Pt5

Pt5

RAMP AND SOAK SEGMENTS TIME (1 to 5): Set of
5 time intervals in minutes (9999 max.) for the 5
segments of the ramp and soak program.

Pe1

Pe1

Pe1

Pe1

Pe5

Pe5

Pe5

Pe5

RAMP AND SOAK EVENT (1 to 5): Set of 5 values
that define which alarms must be activated during a
ramp and soak program segment.

Alarm function depends on “

rS

rS

rS

rS

” setting (Table 3).

lp

lp

lp

lp

LINK TO PROGRAM: Number of the next profile
program to be linked to follow the current profile.
Profiles can be linked to make larger programs of up
to 49 segments.

7.5

ALARM CYCLE

Fva1

Fva1

Fva1

Fva1

ALARM 1 FUNCTION: Select options from Table 3.

Fva2

Fva2

Fva2

Fva2

ALARM 2 FUNCTION: Select options from Table 3.

Fva3

Fva3

Fva3

Fva3

ALARM 3 FUNCTION: Select options from Table 3.

Fva4

Fva4

Fva4

Fva4

ALARM 4 FUNCTION: Select options from Table 3.

bla1

bla1

bla1

bla1
bla2

bla2

bla2

bla2
bla3

bla3

bla3

bla3
bla4

bla4

bla4

bla4

ALARM BLOCK 1 TO 4: This function blocks the
alarm at power-up when the units is first energized.

YES enables and NO inhibits this blocking function.
When enabled the alarm will not be active at power-
up waiting for PV (Process Variable) to reach a non-
alarm situation. From this point on the alarm will be
free to actuate should a new alarm situation occur.

xya1

xya1

xya1

xya1

ALARM 1 HYSTERESIS: Defines the differential
range between the PV value at which the alarm is
turned on and the value at which it is turned off (in
engineering units).

xya2

xya2

xya2

xya2

ALARM 2 HYSTERESIS: Same as above.

xya3

xya3

xya3

xya3

ALARM 3 HYSTERESIS: Same as above.

xya4

xya4

xya4

xya4

ALARM 4 HYSTERESIS: Same as above.

A1t1

A1t1

A1t1

A1t1

ALARM 1 TIME 1: Defines the time (6500 sec. max.)

during which the alarm 1 output will be

ON

when alarm

1 is active. Program zero to disable this function.

A1t2

A1t2

A1t2

A1t2

ALARM 1 TIME 2: Defines the

OFF

state time for the

alarm 1 output, after being

ON

during the time

selected on ALARM 1 TIME 1. Program zero to
disable this function.

A2t1

A2t1

A2t1

A2t1

ALARM 2 TIME 1: Defines the time (6500 sec. max.)

during which the alarm 1 output will be

ON

when alarm

1 is active. Program zero to disable this function

A2t2

A2t2

A2t2

A2t2

ALARM 2 TIME 2: Defines the time during which the

alarm 2 output will be, after being

ON

during the time

selected on ALARM 2 TIME 1. Program zero to
disable this function. Table 4 shows the advanced
features that can be achieved with these time
functions.

7.6

CONFIGURATION CYCLE

type

type

type

type

INPUT TYPE: Selects the input signal type to be
connected to the process variable input. Refer to
Table 1.

This is the first parameter to be set.

dppo

dppo

dppo

dppo

DECIMAL POINT POSITION: For input types 16, 17,
18 or 19 only. Selects the decimal point position to
be viewed in both PV and SV.

vn

vn

vn

vn

I

I

I

I

t

t

t

t

TEMPERATURE INDICATION IN ºC OR ºF: Selects

the display indication to be in ºC or ºF. Only available
if input type is other than 16, 17, 18 or 19.

offs

offs

offs

offs

SENSOR OFFSET: Offset value to be added to the
PV to compensate sensor error. Default value: zero.

spll

spll

spll

spll

SET POINT LOW LIMIT:

- Linear inputs: Sets the lower range for SV and PV
indication.

- T/C and Pt100 inputs: sets the lower range for SV.

sp

sp

sp

spxl

xl

xl

xl

SET POINT HIGH LIMIT:

- Linear inputs: Sets the upper range for SV and PV
indication.

- T/C and Pt100 inputs: sets the upper range for SV.

rsll

rsll

rsll

rsll

REMOTE SET POINT LOW LIMIT: Selects the lower
range for indication of the Remote Setpoint.

rsxl

rsxl

rsxl

rsxl

REMOTE SET POINT HIGH LIMIT: Selects the
upper range for indication of the Remote Setpoint.

bavd

bavd

bavd

bavd

DIGITAL COMMUNICATON BAUD RATE
SELECTION:
0: 1200 bps; 1: 2400 bps; 2: 4800 bps; 3: 9600 bps;
4: 19200 bps.

addr

addr

addr

addr

SLAVE ADDRESS SELECTION: Identifies a slave in
the network. The possible address numbers are from
1 to 247.