NOVUS FieldLogger Register User Manual

Page 6

Advertising
background image

FieldLogger Register

NOVUS AUTOMATION

6/8

0104

Bytes 0 and 1 of channel 6 string (tag)

0105

Bytes 2 and 3 of channel 6 string (tag)

0106

Bytes 4 and 5 of channel 6 string (tag)

0107

Bytes 6 and 7 of channel 6 string (tag)

0108

Bytes 0 and 1 of channel 7 string (tag)

0109

Bytes 2 and 3 of channel 7 string (tag)

0110

Bytes 4 and 5 of channel 7 string (tag)

0111

Bytes 6 and 7 of channel 7 string (tag)

0112

Bytes 0 and 1 of channel 8 string (tag)

0113

Bytes 2 and 3 of channel 8 string (tag)

0114

Bytes 4 and 5 of channel 8 string (tag)

0115

Bytes 6 and 7 of channel 8 string (tag)

0116

Bytes 0 and 1 of the engineering unit of channel 1

0117

Bytes 2 and 3 of the engineering unit of channel 1

0118

Bytes 4 and 5 of the engineering unit of channel 1

0109

Bytes 6 and 7 of the engineering unit of channel 1

0120

Bytes 0 and 1 of the engineering unit of channel 2

0121

Bytes 2 and 3 of the engineering unit of channel 2

0122

Bytes 4 and 5 of the engineering unit of channel 2

0123

Bytes 6 and 7 of the engineering unit of channel 2

0124

Bytes 0 and 1 of the engineering unit of channel 3

0125

Bytes 2 and 3 of the engineering unit of channel 3

0126

Bytes 4 and 5 of the engineering unit of channel 3

0127

Bytes 6 and 7 of the engineering unit of channel 3

0128

Bytes 0 and 1 of the engineering unit of channel 4

0129

Bytes 2 and 3 of the engineering unit of channel 4

0130

Bytes 4 and 5 of the engineering unit of channel 4

0131

Bytes 6 and 7 of the engineering unit of channel 4

0132

Bytes 0 and 1 of the engineering unit of channel 5

0133

Bytes 2 and 3 of the engineering unit of channel 5

0134

Bytes 4 and 5 of the engineering unit of channel 5

0135

Bytes 6 and 7 of the engineering unit of channel 5

0136

Bytes 0 and 1 of the engineering unit of channel 6

0137

Bytes 2 and 3 of the engineering unit of channel 6

0138

Bytes 4 and 5 of the engineering unit of channel 6

0139

Bytes 6 and 7 of the engineering unit of channel 6

0140

Bytes 0 and 1 of the engineering unit of channel 7

0141

Bytes 2 and 3 of the engineering unit of channel 7

0142

Bytes 4 and 5 of the engineering unit of channel 7

0143

Bytes 6 and 7 of the engineering unit of channel 7

0144

Bytes 0 and 1 of the engineering unit of channel 8

0145

Bytes 2 and 3 of the engineering unit of channel 8

0146

Bytes 4 and 5 of the engineering unit of channel 8

0147

Bytes 6 and 7 of the engineering unit of channel 8

0152

Decimal point position for channels

0199

Software version

NOTES ABOUT REGISTERS

Registers 00 to 07:

They keep the continuously updated value of readings from their
respective input channels. The speed of such update depends on the
number of channels enabled and the input type selected for such
channels. As the register is constantly scanning inputs, the higher the
number of active channels the higher the number of inputs that will
be read until the device reads the same channel again, decreasing
the update speed. Besides, channels configured as Pt100 are read
twice each, as part of a compensation algorithm of the cable
resistance. In cases where there is only one active channel (non-
defined as Pt100), this channel is updated at every 0.2 seconds (best
rate). In the case of eight Pt100 channels (worst rate), complete
scanning of channels takes 0.95 seconds.

The signal of the value read is represented as complement of 2.

In cases with resolutions in tenth of degrees, such as Pt100 and
thermocouples, the value is read without the decimal point (multiplied
by 10), for protocol constraints. The same way, the decimal point is
disregarded in linear inputs (4-20 mA e 0-50 mV).

Register 08:

Reports if there is an alarm event in some of the channels and if the
event corresponds to a Low or High alarm.

byte high:

byte low:

Registers 10 to 13

Report A/D conversion errors.
byte high

odd channel:

byte low

even channel:

Same as byte high for the adjacent channel.