Foundation requirements – Goulds Pumps 3298 - IOM User Manual

Page 21

Advertising
background image

Installation

Foundation requirements

Precautions

CAUTION:
If your pump is a Model NM3171, NM3196, 3198, 3298, V3298, SP3298, 4150, 4550, or 3107 there is a
possible risk of static electric discharge from plastic parts that are not properly grounded. If the pumped
fluid is non-conductive, drain and flush the pump with a conductive fluid under conditions that will not
allow for a spark to be released to the atmosphere.

Requirements

• The foundation must be able to absorb any type of vibration and form a permanent, rigid

support for the unit.

• The location and size of the foundation bolt holes must match those shown on the

assembly drawing provided with the pump data package.

• The foundation must weigh between two and three times the weight of the pump.

• Provide a flat, substantial concrete foundation in order to prevent strain and distortion

when you tighten the foundation bolts.

• Sleeve-type and J-type foundation bolts are most commonly used. Both designs allow

movement for the final bolt adjustment.

Sleeve-type bolts

1. Baseplate
2. Shims or wedges
3. Foundation
4. Sleeve
5. Dam
6. Bolt

J-type bolts

1. Baseplate
2. Shims or wedges
3. Foundation
4. Dam
5. Bolt

3298 Family Installation, Operation, and Maintenance Manual

19