Warning, Leak test, evacuation & release of refrigerant, Electrical precautions – Comfort-Aire VMH 24 SD User Manual

Page 11: Caution

Advertising
background image

11

Heat Controller

VMH 09/12/18/24 SD Inverter Mini-Split

Leak Test, Evacuation & Release of Refrigerant

The condensing unit is supplied with a R-410a

factory approximately 25 ft. (7.6m) of line charge,

sufficient for most matching evaporator units.

Charge must be added for interconnecting tubing.

See Field Charging Section of this manual.

The unit’s service valves are shipped in the closed

position and should not be opened until final

connections and evacuation are completed.

WARNING

It is illegal to discharge refrigerant into the

atmosphere. Use proper reclaiming methods

and equipment when working on the refrigerant

containing parts of the unit. Service should be

performed by a QUALIFIED service agency and

certified technicians.

Electrical Precautions

1. Refer to the unit’s rating plate for power supply voltage. Ensure adequate electrical supply

is available.

2. Ensure the air conditioner is properly grounded.
3. Connect wiring to the unit according to the electrical diagram located on the unit.
4. All wiring must comply with local and national electrical codes and be installed by a quali-

fied electrician.

5. An individual branch circuit must be available.
6. Properly size the HACR breaker/fuse based on nameplate date.
7. Improper connections and inadequate grounding can cause injury or death.
8. Connect all wiring tightly. Loose wiring may cause overheating at connection points and

create a possible fire hazard.

9. Match terminal strip numbers/labels and colors between indoor and outdoor wiring. Errone-

ous wiring may cause fire/shock.

10. Always use strain reliefs and outdoor cable cover to protect wiring.

CAUTION

The recommended procedure for leak test, evacuation,

and release of refrigerant is outlined below:

1. Complete the final piping connections to the indoor

and outdoor units using high temperature brazing

alloy.

2. Connect a charging manifold to the service ports

provided at the service valves.

3. Pressurize the lines and evaporator with nitrogen

and leak check all connections with soap bubbles.

Repair as necessary any faulty joints. If brazing is

required be sure to RELEASE THE NITROGEN

FIRST. Re-test as needed.

4. Connect a vacuum pump to the manifold center

connection, start the pump and open the manifold

valves.

5. Evacuate to 500 microns or less for a minimum of

30 minutes. Close the manifold valves and shut off

the pump. Note the vacuum reading and wait 15

minutes. Take a new vacuum reading. A reading

of 800 microns or higher indicates the presence of

moisture or a leak.

6. Repair as necessary and repeat steps 3, 4 & 5.

7. Confirm that manifold valves are closed and

disconnect the vacuum pump.

8. Remove the caps from the services valves. Open

the valves to the fully ‘back-seat’ position. Replace

service valve caps and tighten.

Advertising
This manual is related to the following products: