Heat Controller

VMH 09/12/18/24 SD Inverter Mini-Split

Electrical Work

INdOOR/OUTdOOR

COMMUNICATINg CAbLE

Indoor Wiring

1. Wiring must conform to local and national electric

codes

2. Lift the indoor unit’s panel up, remove the

electrical box cover by loosening the screw as

shown in (Fig.22).

3. Connect each conductor to the terminal of the

indoor unit (L1, L2, S and Ground) based on the

labels of each terminal (Fig. 23).

4. Use strain relief to secure the cable (Fig. 23).
5. Ensure the wire color and location to and from

each terminal are identical between the indoor

and outdoor terminal strips.

6. Wrap any loose cables not connected with

terminals with electrical tape, so that they will not

touch any electrical components.

7. Refer to the wiring diagram located on the

outdoor unit and/or under the front panel of the

indoor unit for proper wiring

8. Heat Controller recommends using 600V THHN

14AWG/4 conductor unshielded stranded copper

cable, however local and national codes for wire

should always be followed based on your specific

application.

Fig. 22

Fig. 23

Panel

Electrical box cover

Terminal block of indoor unit

or

To outdoor unit

To outdoor unit