Refrigerant line installation, Piping and insulating – Comfort-Aire VMH 24 SD User Manual

Page 8

Advertising
background image

8

VMH 09/12/18/24 SD Inverter Mini-Split

Heat Controller

4. Refrigerant Line Installation

A. Remove the knockout from the desired side

of the unit that the line set will be routed from.

The lines from the unit can be routed either

left or right, left back or right back (Fig. 14).

B. Remove the clamp (Fig. 14) before attempt-

ing the bend the line set to prevent kinks.

The clamp may be replaced and used to hold

the line set in place, but this depends on the

routing direction of the line set and whether it

is needed, taking into account the line’s bend

radius.

C. Loosley run the line set connections from the

indoor unit through the hole in the wall.

D. Hang the unit onto the top flanges of the wall

bracket. Ensure the unit is properly seated.

(Fig. 15)

E. Keep the unit away from the wall to prevent

the line set from being kinked or crushed, use

a piece of styrofoam as a spacer between the

back of the unit and the wall. (Fig. 16)

F. Feed the condensate drain line and refriger-

ant line set through the hole such that the unit

can sit flush against the wall then remove the

spacer.

G. Push the bottom of the unit up and onto the

lower flanges of the wall bracket. Ensure that

unit is properly sealed.

H. Be sure that the overall installation of the

indoor unit and installation plate and flush

against the wall and level.

5. Piping and insulating

A. Bundle the tubing, connecting cable*, and drain

hose with tape or wire ties as shown in (Fig.17).

B. Be sure to arrange the drain line such that it

is at the lowest point within the bundle as they

exit the unit and hole in the wall to the out-

doors. (Fig. 17)

C. Because the condensed water from rear of

the indoor unit is gathered in the ponding. Do

not put anything else in this area.

E. Insulated the liquid line and suction lines

separately.

Fig. 15

Fig. 16

Spacer

Top Flange

Bottom Flange

Ponding box

Tape/wire tie

Line set

Drain line

*Connecting

Cable

Fig. 17

Fig. 14

Right

Knockout

Clamp

Knockout

Right back

Left Back

Left

Indoor Unit

Advertising