Indoor unit installation – Comfort-Aire VMH 24 SD User Manual

Page 7

Advertising
background image

7

Heat Controller

VMH 09/12/18/24 SD Inverter Mini-Split

Fig. 9

Wall Bracket should be

flush with the interior wall

Model

R

L

H

Hole Diameter

VMH 24

(10.8in)

275mm

(10.8in)

275mm

(1.8in)

45mm

02.56 in

(65mm)

Fig. 8

Indoor unit installation

1. Wall Bracket Mounting

A. There are two tabs on the back of the

indoor unit that hold the wall bracket onto

the unit. Press them down with a flat head

screwdriver to release the wall bracket from

the back of the unit.

B. Mount the wall bracket flush on structural parts

(studs) of the wall with proper unit clearances

in consideration. (Fig. 1 and Fig. 9)

NOTE: Any space between the unit and the

wall may cause noise or vibration.

C. Screw the wall bracket onto the wall with

type “A” self-tapping screws. If the wall

is made of brick, concrete or the like, drill

1/4” (5mm) diameter pilot holes in the wall.

Use anchors in conjunction with mounting

screws.

NOTE:

• Drill holes in the wall according to the stud

locations and corresponding mounting points

on the actual wall bracket that comes with your

unit. Wall brackets may vary by model and

specifications are subject to change.

• It is important to use all screws provided to

seure the wall bracket to the wall.

2. Create Opening for refrigerant and

condensate lines

A. Determine hole position according to the

wall bracket that comes with your unit, the

unit’s required clearances (Fig. 1) and which

direction (left/right) the lines will be routed

from the back of your unit (Fig. 14). Drill

2.5”(65mm) hole angled downward (approx.

45°) toward the outdoors. (Fig. 11).

NOTE: Ensure that neither studs nor plumbing

are located directly behine the propsed hole

location.

B. Always use a conduit to route the piping

though the hole in the wall. Properly seal

the hole after routing the pipes through to

prevent debris, insects, or small animals

from entering.

3. Condensate Drainage

A. Run the drain hose sloping downward. Do not

install the drain hose as illustrated in Fig.12.

B. When extending the drain hose, with locally

purchased hose, insulate the connection

with armaflex or similar pipe insulation

material. (Fig. 13)

Fig. 10

Fig. 12

Fig. 11

45°

Fig. 13

Indoor

Outdoor

Wall

Wall Cap

Extension drain-

hose

Wall

Drain hose

Pipe Insulation

Do not block water flow by a rise

Do not put the end of

drain hose into water

Model

R

L

H

Hole Diameter

VMH 09

(4.3in) 110mm

(7.1in) 180mm

(1.8in)

45mm

02.56 in

(65mm)

VMH 12

(4.3in) 110mm

(5.5in) 140mm

VMH 18

(5.3in) 135mm

(10.2in) 260mm