Warning – Comfort-Aire CMA36SB-1 User Manual

Page 11

Advertising
background image

11

Heat Controller

Horizontal/Side Discharge Condensing Units

The length of refrigerant lines and the number of

bends determine the pressure drop which affects

capacity and efficiency of the system and oil return

to the compressor. The outdoor unit connections

are flare type. Tube size should always be the

same diameter as the connections provided at

the service valves. Up sizing of lines can result

in inadequate oil return to the compressor and

excessive refrigerant charge and will void the

warranty

[See Table 1].

Choose a location that places the condensing

unit as close to the indoor unit as possible. The

maximum separation is dependent on model.

Use only clean refrigeration grade tubing. Avoid

piping on wet or rainy days. Always keep the tube

ends capped until you are ready to make the final

connections. Remove burrs from cut ends of tubing.

Use tube benders to avoid kinking.

Insulate the suction line with Armaflex or equivalent

with a wall thickness of at least 3/8”. Support the

tubing adequately to avoid sags that can trap oil.

Isolate the tubing so as not to transmit noise to the

building structure. Avoid sharp edges that could cut

the tubes. Maximum vertical lift (compressor above

evaporator) is dependent on model. Trap risers with

a ‘P’ trap every 10 feet.

REFRIGERANT PIPING

LEAk TEST,

EVACUATION

& RELEASE OF

REFRIGERANT

The condensing unit is supplied with R-410a

charge sufficient for most matching evaporator

units. Charge must be added for interconnecting

tubing.

The unit’s service valves are shipped in the closed

position and should not be opened until final

connections and evacuation are completed.

The recommended procedure for leak test,

evacuation, and release of refrigerant is

outlined below:

1. Complete the final piping connections to the

indoor and outdoor units using high temperature

brazing alloy.

2. Connect a charging manifold to the service ports

provided at the service valves.

3. Pressurize the lines and evaporator with

nitrogen and leak check all connections with

soap bubbles. Repair as necessary any

faulty joints. If brazing is required be sure to

RELEASE THE NITROGEN FIRST. Re-test as

needed.

4. Connect a vacuum pump to the manifold center

connection, start the pump and open the

manifold valves.

5. Evacuate to 500 microns or less for a minimum

of 30 minutes. Close the manifold valves and

shut off the pump. Note the vacuum reading and

wait 15 minutes. Take a new vacuum reading. A

reading of 800 microns or higher indicates the

presence of moisture or a leak.

6. Repair as necessary and repeat steps 3, 4 & 5.

7. Confirm that manifold valves are closed and

disconnect the vacuum pump.

8. Remove the caps from the services valves.

Open the valves to the fully ‘back-seat’ position.

Replace service valve caps and tighten.

WARNING

It is illegal to discharge refrigerant into the

atmosphere. Use proper reclaiming methods

and equipment when working on the refrigerant

containing parts of the unit. Service should be

performed by a QUALIFIED service agency and

certified technicians.

Refrigerant Piping

Model No.

CMA 18 CMA 24 CMA 30 CMA 36

Liquid-Gas

In. 1/4 - 1/2

3/8 - 3/4

Max. Refrigerant

Line Length*

Ft.

82

98

Max. Elevation

Vertical Lift**

Ft.

33

49

*Minimum pipe length must not be less that 15 feet.

** “P” trap risers every 10 ft. when outdoor unit is installed

above indoor unit.

Advertising
This manual is related to the following products: