Horizontal/Side Discharge Condensing Units

Heat Controller

4/2014

INITIAL START-UP & CHECkS

Operation of the unit is automatic and will provide

cooling depending on the setting of the thermostat.

IMPORTANT!

All panels must be installed, main power turned

on and the thermostat properly connected before

operating the unit.

1. System check - set thermostat system switch to

“Off” position and fan switch to “Auto” position.

Turn the power supply breaker on.

2. Set the fan switch to “On,” blower should

operate.

3. Return the fan switch to “Auto”. Blower should

shut off. Set the system switch to “Cool” and

lower thermostat set point to coldest setting.

The compressor, condenser fan, and evaporator

blower should all come on. Cool air will be

supplied after a couple of minutes of run time.

4. Proceed to the “FIELD CHARGING” section of

these instructions.

FIELD CHARGING

Unit performance, efficiency, and life depends,

to a large extent, on a proper system charge.

Time spent on getting the charge right at start-up

will payoff in the long run. Operating conditions

such as voltage, air flow, evaporator coil size,

and indoor and outdoor temperature and humidity

all have an effect on the system pressures and

superheat conditions.

Charge must be added for the interconnecting

tubing. Evaporator coils require thermostatic

expansion valves. These units should be critically

charged to ensure proper performance. Some

systems may require additional charging of

refrigerant, depending on line set lengths.

FINAL INSPECTION

Do a final visual inspection of the entire installation

and complete any final details and clean up.

Review Unit Operation with the homeowner/user.

The pressure/temperature chart can be used as a

reference to ensure performance.

2XWGRRU$PELHQW7HPSHUDWXUH963UHVVXUH

2XWGRRU7HPSHUDWXUH

1RWH³,'7´ ,QGRRU7HPSHUDWXUH

³2'7´ 2XWGRRU7HPSHUDWXUH

5HPRYHUHIULJHUDQWLIWKHSUHVVXUHLVDERYHWKHFKDUWYDOXH

$GGUHIULJHUDQWLIWKHSUHVVXUHLVEHORZWKHFKDUWYDOXH

36,

oz/ft

R(oz): Additional refrigerant to be charged

L(ft): The length of the liquid pipe

T(oz): The quantity of the charged refrigerant

per additional foot

0.16

0.32