Horizontal/Side Discharge Condensing Units

Heat Controller

UNIT LOCATION AND MOUNTING:

Choose a location that places the condensing

unit as close to the indoor unit as possible. The

maximum unit separation and vertical lift (compressor

above evaporator) must be taken into account

[See

Fig 1]. Do not exceed allowable pipe lengths.

NOTE: Oil traps must be installed every 10ft. when

the outdoor unit is installed above the indoor unit.

Install the outdoor unit on a rigid surface, able to

withstand the unit’s weight, such as a concrete slab.

If the installation location allows the unit to be

exposed to strong winds (such as sea side

applications), ensure that the unit has a barrier from

the wind

[See Fig. 2]. This will assist with the proper

operation of the fan by obstructing strong gusts of

wind from entering the unit’s cabinet.

Avoid areas where water, snow, or ice may fall

from a roof onto the unit. In climates where snow

is a consideration, locate the unit away from areas

prone to drifting. Ensure the location of the unit will

not be subject to snow drifts, heavy accumulation

of snow or leaves or other seasonal debris. If

unavoidable, provide the awning for the unit.

OUTDOOR UNIT INSTALLATION

An awning can be built over the outdoor unit to

prevent direct sunlight or rain exposure or snowfall.

Ensure that the awning is at least 2 ft. above the

top of the unit’s housing.

During heating and defrost modes, the condensate

should be properly drained away from the unit.

Insure free flow of air into and out of the unit.

Inlets/outlets should stay clear of obstructions such

as walls and shrubs. Minimum clearances must be

adhered to

[See Fig. 4 & 5 on page 7].

Do not locate two or more units in a way that will

block air flow or in a way that hot air from one unit

will blow into a nearby unit

[See Fig. 3].

Fig. 1

Refrigerant Piping

Model No.

CMA 18 CMA 24 CMA 30 CMA 36

Liquid-Gas

In. 1/4 - 1/2

3/8 - 3/4

Max. Refrigerant

Line Length*

Ft.

82

98

Max. Elevation

Vertical Lift**

Ft.

33

49

*Minimum pipe length must not be less that 15 feet.

** “P” trap risers every 10 ft. when outdoor unit is installed

above indoor unit.