Caution, Unit wiring – Comfort-Aire CMA36SB-1 User Manual

Page 8

Advertising
background image

8

Horizontal/Side Discharge Condensing Units

Heat Controller

UNIT WIRING

ELECTRICAL WIRING

AND SUPPLY VOLTAGE:

All electrical wiring must be done according to

NEC and local codes. Nameplate data indicates

the operating voltage, phase, ampacity, maximum

over current protection, and minimum voltage.

The contractor is to provide an individual branch

circuit for over current protection for the unit as

required by code. Run power supply wiring through

a weatherproof disconnect box and conduit to the

unit connection. Disconnects are required to be

within sight and easy reach of the unit (usually

within 3 feet).

Check the unit wiring diagram for the number of

conductors required. Route neatly and protect from

sharp edges and damage.

Inadequate wiring and/or improper electrical

supply will likely result in failure of the compressor

and other electrical components and voids the

warranty.

NOTE: The supply voltage must be consistent

with the rated voltage of the air conditioner, not

to exceed +/- 10%. Ensure the unit is properly

grounded.

CAUTION

Incorrect wiring connections may cause

electrical parts to malfunction. All wiring must

comply with local and national electrical

codes and be installed by qualified and skilled

electricians.

Outdoor unit wiring connection

1. Remove the electrical control cover from the

outdoor unit.

2. Connect the cables to the terminals as

identified with their respective designated

terminal spaces on the terminal block of indoor

and outdoor units. 600V THHN 14 AWG/4

conductor unshielded stranded copper cable

is recommended, however NEC/local codes

prevail.

3. To prevent the entrance of water into outdoor

unit, form a loop in the cable [See Fig. 6].

4. Insulate any unused conductors with PCV/

Electrical tape, so that they do not touch any

other exposed electrical or metal parts.

Advertising
This manual is related to the following products: