Command Reference: Outlet Commands

18

Command Line Interface (CLI) User’s Guide

poweroffdelay

Syntax (to read the power-off delay):

poweroffdelay [outlet|range][,outlet|range...]

Syntax (to set the power-off delay):

poweroffdelay outlet|range[,outlet|range...] time|never

Description:

Set or read the power-off delay (the

time in seconds that the PDU waits after a
command is issued before it restores power to an
outlet). If you do not specify any outlets, the
power-off delay settings of all outlets to which you
have access are read. To set the power-off delay,
you must specify one or more outlets.

Parameters:

Output Format, reading power-off delay:

OK
outlet_number: outlet_name: Power off delay is
time seconds.

Output Format, setting power-on delay:

OK
outlet_number: outlet_name: Setting power off
delay to time seconds.

Error Messages:

E101, E104

outlet An outlet name or number. If you specify a

name that contains a space character, you must

enclose the name in quotation marks.

range A range of outlet numbers, with a hyphen

separating the starting number from the

ending number.

time

The power-off delay in seconds to set for the

specified outlets.

never Sets the specified outlets to remain on. This

value is not case-sensitive.