Nearoverloadwarning – APC Command Line Interface User Manual

Page 30

Advertising
background image

Command Reference: Switched Rack PDU Commands

26

Command Line Interface (CLI) User’s Guide

nearoverloadwarning

Syntax (to read the nearoverload alarm

threshold):

nearoverloadwarning [phase_number]

Syntax (to set the nearoverload warning

threshold):

nearoverloadwarning phase_number current

Description:

Set or read the near-overload

warning threshold.

Parameters:

Access:

Administrator or device manager

(device-only user).

Output format, reading the near-overload

alarm threshold:

OK
Near overload warning threshold is currentA.

Output format, setting the near-overload alarm

threshold:

OK
Setting near overload warning threshold for
phase_number to currentA.

Error Messages:

E101, E104

phase_number The number (1, 2, or 3) of the phase

whose near-overload warning

threshold you want to read or set. The

default is phase 1.

current

The threshold, in amps, to set for the

phase specified as phase_number.

Advertising