Command Reference: Switched Rack PDU Commands

28

Command Line Interface (CLI) User’s Guide

overloadrestriction

Syntax to read the overload restriction:

overloadrestriction [phase_number]

Syntax to set the overload restriction:

overloadrestriction phase_number setting

Description:

When the overload restriction is set

to on, the command prevents outlets from turning
on while the overload alarm threshold is violated.

• To read the current setting, omit setting in the

command line.

• To change the current setting, include the

phase number and the new value for setting
(on or off) in the command line.

Access:

Administrator and device manager

(device-only user).

Parameters:

Output Format when reading the setting:

OK
Overload restriction is setting for phase_number.

Output Format when changing the setting:

OK
Setting overload for phase_number to setting.

Error Messages:

E101, E104

phase_number The number (1, 2, or 3) of the phase

whose overload restriction setting you

want to read or set. If you omit the

phase number when reading the

setting, the command by default reads

the setting for phase 1.

setting

The available settings, on and off, are

not case-sensitive.