Command Reference: Switched Rack PDU

Command Line Interface (CLI) User’s Guide

25

lowloadwarning

Syntax (to read the low-load warning threshold):

lowloadwarning [phase_number]

Syntax (to set the low-load warning threshold):

lowloadwarning phase_number current

Description:

Set or read the low-load warning

threshold.

Parameters:

Access:

Administrator or device manager

(device-only user).

Output format, reading the low-load warning

threshold:

OK
Low load warning threshold is currentA.

Output format, setting the low-load warning

threshold:

OK
Setting low load warning threshold for
phase_number to currentA.

Error Messages:

E101, E104

name

Syntax:

name outlet new_name

Description:

Assign a name to an outlet or a

system name to the Switched Rack PDU.

Access:

Administrator or device manager

(device-only user).

Parameters:

Output Format:

OK
outlet: Setting name to new_name

Error Message:

E101

phase_number The number (1, 2, or 3) of the phase

whose low-load warning threshold

will be read or set. The default is 1.

current

The threshold, in amps, to set for the

phase specified as phase_number.

outlet

An outlet number or, to specify the system

name of the Switched Rack PDU, the

string

master

(not case-sensitive).

new_name A name to assign to the outlet or, if master

was specified as outlet, the system name

to assign to the Switched Rack PDU. The

name can be up to 23 printable ASCII

characters. If the name contains one or

more spaces, you must enclose the name

in quotation marks.