Command Reference: Outlet Commands

Command Line Interface (CLI) User’s Guide

19

powerondelay

Syntax (to display the power-on delay):

powerondelay [outlet|range][,outlet|range...]

Syntax (to set the power-on delay):

powerondelay outlet|range[,outlet|range...] time|never

Description:

Set or read the power-on delay (the

time in seconds that the PDU waits after a
command is issued before it restores power to an
outlet). If you do not specify any outlets, the
power-on delay settings of all outlets to which you
have access are read. To set the power-on delay,
you must specify one or more outlets.

Parameters:

Output format, reading power-on delay:

OK
outlet_number: outlet_name: Power on delay is
time seconds.

Output format, setting power-on delay:

OK
outlet_number: outlet_name: Setting power on
delay to time seconds.

Error Messages:

E101, E104

outlet An outlet name or number. If you specify a

name that contains a space character, you must

enclose the name in quotation marks.

range A range of outlet numbers, with a hyphen

separating the starting number from the

ending number.

time

The power-on delay in seconds to set for the

specified outlets.

never Sets the specified outlets to remain off. This

value is not case-sensitive.

Advertising