Controlling the VS-88HC

17

7.2 Controlling via RS-485

You can control up to eight

VS-88HC units via an RS-485 controller, for

example, a PC (equipped with an RS-485 interface) or a Master

Programmable Remote Control system such as the Kramer

RC-3000.

To connect an

RC-3000 to a VS-88HC unit (see Figure 8), connect the

RS-485 terminal block port on the

RC-3000 to the RS-485 port on the

VS-88HC unit, as follows:

1. Connect the “A” (+) PIN on the RS-485 rear panel port of the

RC-3000 to the

“A” (+) PIN on the RS-485 rear panel port of the

VS-88HC unit

2. Connect the “B” (-) PIN on the RS-485 rear panel port of the

RC-3000 to the

“B” (-) PIN on the RS-485 rear panel port of the

VS-88HC unit

3. If shielded twisted pair cable is used, the shield may be connected to the “G”

(Ground) PIN on one of the units (for example, on the

RC-3000)

To cascade up to eight individual

VS-88HC units, via RS-485, as illustrated

in Figure 8, do the following:

1. Connect the component video sources and acceptors, as well as the

appropriate digital audio sources and acceptors, as section 6.1 describes.

2. Connect the RS-485 terminal block port on the first

VS-88HC unit to

the RS-485 port on the second

VS-88HC unit and so on, connecting all

the RS-485 ports.

7.2.1

Set the Dipswitches

Set the dipswitches, as section 6.3 describes:

Assign a unique self address #

1

(from 1 to 8) for each

VS-88HC unit,

according to Table 6

Set DIP 4 ON on the

VS-88HC unit located at the end of the line

(terminating the RS-485 line at 120 ).

Set DIP 4 OFF on the other

VS-88HC units

1 In any order