6. Commissioning, operation

6.3 Message structure

In the send message the transmission of the measured value, error detection and service requests are

combined. The D-1x-7 supports only DP-V0 and therefore a cyclic data exchange.
Below, the encoding of the individual elements is clarified:

The representation is not carried out as a two's complement.

Send message

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Pressure

value MSB

with sign

Pressure

value

LSB

Factor,

Unit

Error status Error code

Service

request

Service

response 1

Service

response 2

Measured value

Error detection

Services

Measured value

Number format of the measured value: 16 bit integer (sign and magnitude representation)

Pressure value MSB (Byte 1): Bit 7 contains the algebraic sign

Bit 6 ... 0 contains the highbyte of the measured value

Pressure value LSB (Byte 2): contains the lowbyte of the measured value

Factor

(Byte 3): contains the measurement type, unit and exponent

Pressure value MSB (byte 1)

Pressure value LSB (byte 2)

7 6 5 4 3 2 1 0

7 6 5 4 3 2 1 0

Pressure value
(Note the sign bit and factor)
Pressure value sign
0 = positive

1 = negative