WIKA operating instructions pressure transmitter model D-1x-7
2478159.05 12/2011 GB/D/F/E
GB
Zero adjustment, example 2:
A pressure transmitter with a measuring range of -1 ... +2.5 bar has a zero offset of -10 mbar, then one
would correct:
Pressure range -1 ... +2.5 bar
Span: 3.5 bar
Display value 10 mbar too low
Offset: -0.010 bar
Span correction
Output data
Input data
Explanation
0x22
XX
XX
0x22
HI
LO
Read span correction
0x24
HI
LO
0x24
HI
LO
Write span correction
The respective correction value can be calculated as follows:
Correction value = -
Span offset
x 50,000
Span
Correction value: Digit value which is programmed into the instrument via service 0x24.
Span offset: Set span - actual span in bar
Span: Set span MBE - MBA in bar
The changes only take effect after a reset.
6. Commissioning, operation
Correction value = -
Offset x 50,000
Span
Correction value = - -0.010 bar x 50,000
3.5 bar
Correction value = +143
0x008F
Output data
0x23
0x00
0x8F